Controller A sends new configuration to the module.
30
• The controllers that do maintain, but do not 'own' , the module
configuration are similar to Listen-only controllers.
The difference between the controllers is that the controllers that
maintain, but do not own, the module configuration can use a Multicast
or Unicast connection over the EtherNet/IP network.
For more information on Listen-only controllers, see
page
56.
You must be careful when changing the configuration data of an input module
in a multiple-owner scenario. If the configuration data is changed in owner A
and sent to the module, the changed configuration data is accepted as the new
configuration for the module. Owner B continues to listen unaware that any
changes have been made in the behavior of the input module, as illustrated.
Figure 6 - Module Configuration Changes with Multiple Owners
ANALOG OUTPUT
COUNTER
5069-OF8
5069-HSC2xOB4
Compact 5000™ I/O
IMPORTANT A message in Logix Designer application alerts you to the possibility of a
Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
DC INPUT
DC INPUT
DC OUTPUT
DC OUTPUT
5069-IB16
5069-IB16
5069-OB16
5069-OB16
Controller B is unaware of any configuration changes.
multiple owner-controller situation and lets you inhibit the connection
before changing the module configuration. When changing the
configuration for a module with multiple owners, we recommend that you
inhibit the connection.