Communicate with the Module

POINT I/O modules send (produce) and receive (consume) I/O data (messages). You
map this data onto the processor's memory.
These modules produce 6 bytes of input data (scanner Rx) and fault status data. These
modules do not consume I/O data (scanner Tx).
Default Data Map
Message size: 6 Bytes
15 14 13
Produces
Input channel 0 – high byte
(scanner Rx)
Input channel 1 – high byte
Status byte for channel 1
OR UR HHA LLA HA LA
Consumes
No consumed data
(scanner Tx)
Where:
OR = Overrange; 0 = No error, 1 = Fault
UR = Underrange; 0 = No error, 1 = Fault
HHA = High/High Alarm; 0 = No error, 1 = Fault
LLA = Low/Low Alarm; 0 = No error, 1 = Fault
HA = High Alarm; 0 = No error, 1 = Fault
LA = Low Alarm; 0 = No error, 1 = Fault
CM = Calibration Mode; 0 = Normal, 1 = Calibration mode
CF = Channel Fault Status; 0 = No error, 1 = Fault
POINT I/O 2 Current and 2 Voltage Input Analog Modules
12 11 10 09 08 07 06 05
Publication 1734-IN027D-EN-E - December 2018
Input channel 0 – low byte
Input channel 1 – low byte
Status byte for channel 0
CM CF
OR UR HHA LLA HA LA
04 03 02 01 00
CM CF
17