Ownership; Multiple Owners Of Compact 5000 I/O Digital; Input Modules - Allen-Bradley Compact 5000 Series User Manual

I/o digital modules
Table of Contents

Advertisement

Ownership

Standard Modules
DC INPUT
DC INPUT
DC OUTPUT
ANALOG INPUT
5069-IB16
5069-IB16
5069-OB16
5069-IY4
DC INPUT
DC INPUT
DC OUTPUT
5069-IB16
5069-IB16
5069-OB16
UPS
R
R
OK
FAN 1
B
B
RUN
SD
F
F
FORCE
FAN 2
MP
NET B1
LINK B1
NET A1
LINK A1
SA
NET A2
SPEED X1
LINK A2
LINK X1
CompactLogix 5480
Safety Modules
OUTPUT
SIL2 CPU
5069-L3100ERMS2
5069-IB8S
5069-IB8S
5069-OBV8S
Compact GuardLogix
Every I/O module in a Logix 5000 control system must be owned by a
controller, also known as the owner-controller. When a Compact 5000 I/O
digital module is used in a Logix 5000 control system, the owner-controller
performs the following:
ANALOG OUTPUT
5069-OF8
• Stores configuration data for every module that it owns.
• Can reside in a location that differs from the Compact 5000 I/O
digital modules.
• Sends the I/O module configuration data to define module behavior
and begin operation in the control system.
ANALOG INPUT
ANALOG OUTPUT
5069-IY4
5069-OF8
Each Compact 5000 I/O digital module must continuously maintain
communication with its owner-controller during normal operation.
Typically, each I/O module in a system has only one owner-controller. Output
modules are limited to one owner-controller.
Multiple Owners of Compact 5000 I/O Digital Input Modules
OUTPUT
5069-OBV8S
Typically only one owner-controller is connected to a Compact 5000 I/O
digital input module. However, multiple Logix 5000 controllers can connect to
Compact 5000 I/O digital input modules as owner-controllers.
In this case, the following conditions must exist:
• The controllers maintain the same configuration.
• The configuration in each controller uses a Data connection to the
input module.
• The first controller to make a connection to the input module is the
only controller that can change the connection. Therefore, it is 'owns'
the module configuration.
IMPORTANT If the controller that owns the module configuration changes the
Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
Digital Module Operation in a Control System
configuration, the other controllers are not notified of the changes.
For more information, see
Configuration Changes in an Input
Module with Multiple Owners on page
Chapter 1
30.