Fault State Duration After Connection Fault

If you configure the output to transition to a specific value after the connection
breaks, you must define how long the output remains at the specified value
before it transitions to a Final Fault State.
You can configure the output to remain at the specific value for the following
times:
• Forever
• 1 second
• 2 seconds
• 5 seconds
• 10 seconds
After the Fault State Duration time expires, the output transitions to user-
defined Final Fault State Value.

Final Fault State Value

The Final Fault State value defines the value to which the output goes after the
Fault State Duration time expires.
You set the value in the C.Ptxx.FaultFinalState tag. For more information on
module s, see Appendix B,

Output State Once Connection Is Re-established

Once the connection between the owner-controller and output module is re-
established, the output resumes normal operation.
To see where to configure the Connection Fault Handling parameters, see the
following:
• 5069-OA16 module -
• 5069-OB8 module -
• 5069-OB16 and 5069-OB16K modules -
• 5069-OB16F module -
• 5069-OW4I module -
• 5069-OW16 module -
• 5069-OX4I module -