Install the DC-Input/Relay-Output Combination Module

ATTENTION
Do not remove protective debris strip until after the module and all other
equipment near the module is mounted and wiring is complete. Once wiring
is complete and the module is free of debris, carefully remove protective
debris strip. Failure to remove strip before operating can cause overheating.
Maintain spacing from enclosure walls, wireways, and adjacent equipment. Allow 50.8 mm
(2 in.) of space on all sides for adequate ventilation, as shown:
TIP
1762 expansion I/O is only mounted horizontally.
ATTENTION
During panel or DIN-rail mounting of all devices, be sure that all debris
(metal chips or wire strands) is kept from falling into the module. Debris
that falls into the module could cause damage when power is applied to the
module.

Mount the Module on a DIN Rail

The module can be mounted using the following DIN rails: 35 x 7.5 mm
(EN 50 022 - 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).
Before mounting the module on a DIN-rail, close the DIN-rail latch. Press the DIN-rail
mounting area of the module against the DIN-rail. The latch will momentarily open and lock
into place.
Use DIN-rail end anchors (Allen-Bradley part number 1492-EA35 or 1492-EAH35) for
vibration or shock environments.
Publication 1762-IN018B-EN-P - July 2013