Wiring Input Devices To The Nr4 Module - Allen-Bradley SLC 500 1746-NR4 Installation Instructions Manual

Rtd/resistance input module
Hide thumbs Also See for SLC 500 1746-NR4:
Table of Contents

Advertisement

16
SLC 500™ RTD/Resistance Input Module

Wiring Input Devices to the NR4 Module

Signal Wire
Signal Wire
Signal Wire
Signal Wire
Signal Wire
To wire your NR4 module, follow these steps.
1. At each end of the cable, strip some casing to expose the individual wires.
2. Trim the signal wires to 5.08-cm (2-in.) lengths. Strip about 4.76 mm (3/16
in.) of insulation away to expose the end of the wire.
3. At one end of the cable twist the drain wire and foil shield together, bend
them away from the cable, and apply shrink wrap. Then earth ground at the
shield terminal.
4. At the other end of the cable, cut the drain wire and foil shield back to the
cable and apply shrink wrap.
5. Connect the signal wires and cable shield to the NR4 terminal block and the
input.
6. Repeat steps 1 through 5 for each channel on the NR4 module.
Publication 1746-5.17
2-Conductor Shielded Cable
Drain Wire
Foil Shield
(See step 3.)
3-Conductor Shielded Cable
Drain Wire
Foil Shield
(See step 3.)
(See Step 4.)
Signal Wire
Signal Wire
(See Step 4.)
Signal Wire
Signal Wire
Signal Wire

Hide quick links: