Main circuit terminals

2.5
Main circuit terminals
2.5.1
Details on the main circuit terminals of the
inverter
Terminal
Terminal name
symbol
U, V, W
Inverter output
R1/L11,
Power supply for the control
S1/L21
circuit
P/+, N/-
Converter unit connection
Earth (ground)
2.5.2
Details on the main circuit terminals of the
converter unit (FR-CC2-C)
Terminal
Terminal name
symbol
R/L1,
S/L2,
AC power input
T/L3
R1/L11,
Power supply for the control
S1/L21
circuit
P/+, N/-
Inverter connection
Earth (ground)
26
INSTALLATION AND WIRING
Terminal function description
Connect these terminals to a three-phase squirrel cage motor or an PM
motor.
Connected to terminals P/+ and N/-. To retain the fault display and fault
output, or to use the converter unit (FR-CC2-C), remove the jumpers installed
in terminals R1/L11 and S1/L21, and apply external power supply to these
terminals.
When using a separate power supply from R1/L11 and S1/L21, the
necessary power capacity of the separate power supply is 80 VA.
Connect the converter unit (FR-CC2-C).
For earthing (grounding) the inverter chassis. This must be earthed
(grounded).
Terminal function description
Connect these terminals to the commercial power supply.
Connected to the AC power supply terminals R/L1 and S/L2. To retain the
fault display and fault output, remove the jumpers across terminals R/L1 and
R1/L11 and across S/L2 and S1/L21, and supply external power to these
terminals.
When using a separate power supply from R1/L11 and S1/L21, the
necessary power capacity of the separate power supply is 80 VA.
Connect to terminals P/+ and N/- of the inverter.
For earthing (grounding) the converter unit chassis. This must be earthed
(grounded).
Refer
to page
-
40
24
30
Refer
to page
-
40
24
30