Appendix 2 Instructions For Ul And Cul - Mitsubishi Electric F800-E Series Instruction Manual

Separated converter type
Hide thumbs Also See for F800-E Series:
Table of Contents

Advertisement

Appendix 2
(Standard to comply with: UL 508C, CSA C22.2 No.14)
 General Precaution
CAUTION - Risk of Electric Shock -
The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for more than 10 minutes, and check for residual
voltage between terminal P/+ and N/- with a meter etc., to avoid a hazard of electrical shock.
ATTENTION - Risque de choc électrique -
La durée de décharge du condensateur de bus est de 10 minutes. Avant de commencer le câblage ou l'inspection, mettez l'appareil hors tension et attendez plus
de 10 minutes.
 Installation
The FR-F862 inverters with the below types of converter unit have been approved as products for use in enclosure.
Design the enclosure so that the surrounding air temperature, humidity and ambience of the inverter will satisfy the specifications. (Refer to
 Wiring protection
For installation in the United States, Class T, Class J, Class CC, or Class L fuse must be provided, in accordance with the National Electrical Code and any
applicable local codes.
For installation in Canada, Class T, Class J, Class CC, or Class L fuse must be provided, in accordance with the Canadian Electrical Code and any applicable
local codes.
FR-CC2-[ ]
Rated fuse voltage (V)
Fuse maximum allowable rating (A)

Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.
 Wiring to the power supply and the motor
For wiring the input (R/L1, S/L2, T/L3) terminals of the converter unit and output (U, V, W) terminals of the inverter, use the UL listed copper, stranded wires (rated
at 75°C) and round crimp terminals. Crimp the terminals with the crimping tool recommended by the terminal manufacturer.
 Short circuit ratings
Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes, 600 V Maximum.
 Motor overload protection
When using the electronic thermal relay function as motor overload protection, set the rated motor current in Pr.9 Electronic thermal O/L relay.
Operation characteristics of electronic thermal relay function
Pr.9 = 50% setting
of inverter rating
∗1, 2
70
30 Hz
or more
20 Hz
60
10 Hz
6 Hz
0.5 Hz
50
240
180
120
60
52.5%
50
(% to the inverter rated current)
NOTE
• The internal accumulated heat value of the electronic thermal relay function is reset by inverter power reset and reset signal input. Avoid unnecessary reset and power-
OFF.
• Install an external thermal relay (OCR) between the inverter and motors to operate several motors, a multi-pole motor or a dedicated motor with one inverter. Note that
the current indicated on the motor rating plate is affected by the line-to-line leakage current (refer to Instruction Manual (Detailed)) when selecting the setting for an
external thermal relay.
• The cooling effect of the motor drops during low-speed operation. Use a thermal protector or a motor with built-in thermistor.
• When the difference between the inverter and motor capacities is large and the setting is small, the protective characteristics of the electronic thermal relay function will
be deteriorated. In such case, use an external thermal relay.
• A dedicated motor cannot be protected by an electronic thermal O/L relay. Use an external thermal relay.
• Motor over temperature sensing is not provided by the drive.
Instructions for UL and cUL
C355K
C400K
575 V or more
700
800

Pr.9 = 100% setting
of inverter rating
∗2
30 Hz
Operation region
or more
Region on the right of
characteristic curve
20 Hz
Non-operation region
10 Hz
Region on the left of
6 Hz
characteristic curve
0.5 Hz
Characteristic when
electronic thermal relay
function for motor
protection is turned off
(When Pr.9 setting is 0(A))
Range for
the transistor
protection
∗3
105%
100
150
230
Inverter output power (%)
C560K
1000
This function detects the overload (overheat) of the motor and trips the
inverter by stopping the operation of the transistor at the inverter output side.
(The operation characteristic is shown on the left.)

When a value 50% of the inverter rated output current (current value)
is set in Pr.9

The % value denotes the percentage to the rated inverter current. It is
not the percentage to the rated motor current.

Transistor protection is activated depending on the temperature of the
heatsink. The protection may be activated even with less than 150%
depending on the operating conditions.
page
17.)
83
APPENDIX

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents