Terminal connection diagrams
2.4
Terminal connection diagrams
Sink logic
Main circuit terminal
Control circuit terminal
Converter
unit
R/L1
P/+
S/L2
N/-
T/L3
RDI
Control input signals
(No voltage input allowed)
OH
Forward rotation start
RES
Reverse rotation start
SD
Start self-holding selection
PC
+24
Multi-speed
C1
selection
B1
A1
Second function selection
RDB
RDA
RSO
Terminal 4 input selection
IPF
FAN
Contact input common
SE
(Common for external power supply transistor)
24V external power
Common terminal
Frequency setting signals (Analog)
Frequency setting
potentiometer
1/2W1kΩ
Terminal 4 input
(Current input)
Connector for plug-in option connection
For manufacturer
24
INSTALLATION AND WIRING
P/+
N/-
Jumper
R1/L11
S1/L21
Earth
(Ground)
STF
STR
STP(STOP)
RH
High speed
RM
Middle speed
Low speed
JOG
Jog operation
MRS X10
Output stop
RES
Reset
SD
PC
24VDC power supply
+24
supply input
SD
10E(+10V)
10(+5V)
3
2
2
5
1
Auxiliary
(+)
1
input
(-)
(+)
4
(-)
Connector 1 Connector 2
Connector 3
Shorting
wire
PC
S1
S2
SIC
SD
Main circuit
Control circuit
RL
RT
AU
CS
24V
PU
Voltage/current
connector
input switch
ON
USB A
OFF
connector
2
4
0 to 5VDC
Initial value
0 to 10VDC
USB
selectable
0 to 20mADC
mini B
(Analog common)
connector
0 to ±10VDC
Initial value
Ethernet
0 to ±5VDC selectable
connector
Initial value
4 to 20mADC
0 to 5VDC
selectable
0 to 10VDC
U
V
W
Relay output
C1
B1
Relay output 1
(Fault output)
A1
C2
B2
Relay output 2
A2
Open collector output
RUN
Running
SU
Up to frequency
IPF
OL
Overload
FU
Frequency detection
SE
Open collector output common
Sink/source common
F/C
(+)
(CA)
Analog current output
(0 to 20mADC)
(-)
(+)
AM
Analog signal output
5
(0 to ±10VDC)
(-)
So (SO)
SOC
Motor
M
Earth (Ground)