Mitsubishi Electric F800-E Series Instruction Manual page 26

Separated converter type
Hide thumbs Also See for F800-E Series:
Table of Contents

Advertisement


Terminals R1/L11 and S1/L21 are connected to terminals P/+ and N/- with a jumper respectively. When using separate power supply for the
control circuit, remove the jumpers from R1/L11 and S1/L21.

The function of these terminals can be changed with the input terminal assignment (Pr.178 to Pr.189).

Terminal JOG is also used as the pulse train input terminal. Use Pr.291 to choose JOG or pulse.

The X10 signal (NC contact input specification) is assigned to the terminal MRS in the initial setting. Set Pr.599 = "0" to change the input
specification of the X10 signal to NO contact.

No function is assigned in the initial setting. Use Pr.186 for function assignment.

Terminal input specifications can be changed by analog input specification switchover (Pr.73, Pr.267). To input a voltage (0 to 5 V/0 to 10 V), set
the voltage/current input switch OFF. To input a current (4 to 20 mA), set the voltage/current input switch ON. Terminals 10 and 2 are also used
as a PTC input terminal. (Pr.561)

It is recommended to use 2 W 1 k when the frequency setting signal is changed frequently.

The function of these terminals can be changed with the output terminal assignment (Pr.195, Pr.196).

The function of these terminals can be changed with the output terminal assignment (Pr.190 to Pr.194).
 No function is assigned in the initial setting. Use Pr.192 for function assignment.
 The option connector 2 cannot be used because the Ethernet board is installed in the initial status. The Ethernet board must be removed to
install a plug-in option to the option connector 2. (However, Ethernet communication is disabled in that case.)
NOTE
• To prevent a malfunction due to noise, keep the signal cables 10 cm or more away from the power cables. Also, separate the
main circuit cables at the input side from the main circuit cables at the output side.
• After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in an enclosure etc., take caution not to allow chips and other foreign matter to enter the
inverter.
• Set the voltage/current input switch correctly. Incorrect setting may cause a fault, failure or malfunction.
• Terminals S1, S2, SIC, So (SO), and SOC are for manufacturer setting. Do not remove the shorting wires across terminals S1
and PC, terminals S2 and PC, and terminals SIC and SD. When the shorting wires are removed, the inverter does not
operate.
Connection between the converter unit and the inverter
Perform wiring so that the commands sent from the converter unit are transmitted to the inverter without fail. Incorrect
connection may damage the converter unit and the inverter.
For the wiring length, refer to the table below.
Across terminals P and P and terminals N and N
Total wiring length
For the cable gauge of the cable across the main circuit terminals P/+ and N/- (P and P, N and N), refer to
MCCB
MC
Power
supply

Do not install an MCCB across terminals P/+ and N/- (across terminals P and P/+ or across N and N/-). Connecting the opposite polarity of
terminals N/- and P/+ will damage the inverter.

For the terminal used for the X10 signal input, set "10" in any of Pr.178 to Pr.189 (Input terminal function selection) to assign the function.
(The X10 signal is assigned to terminal MRS in the initial setting.)
For the X10 signal, NC contact input specification is selected in the initial setting. Set Pr.599 = "0" to change the input specification to NO
contact.

For the terminal used for the X11 signal input, set "11" in any of Pr.178 to Pr.189 (Input terminal function selection) to assign the function. For
RS-485 or any other communication where the start command is only transmitted once, use the X11 signal to save the operation mode at the
time of an instantaneous power failure.

Always connect terminal RDA of the converter unit and terminal MRS (X10) of the inverter, and terminal SE of the converter unit and terminal SD
(sink logic) of the inverter. Not connecting these terminals may damage the converter unit.
Other control signal cables
Converter unit
(FR-CC2-C)
Inverter

R/L1
P/+
P/+
N/-
N/-
S/L2
R1/L11
S1/L21
T/L3
R1/L11
S1/L21

RDA
MRS(X10)

RDB
IPF
X11
RES
RSO

SD
SE
Terminal connection diagrams
50 m or less
30 m or less
U
V
M
W

INSTALLATION AND WIRING
page
28.
2
25