Mount Transmitter On A Turbine Meter Or Pulse - Emerson Rosemount 705 Quick Start Manual

Wireless totalizing transmitter
Hide thumbs Also See for Rosemount 705:

Advertisement

Quick Start Guide
4.1
Join device to network
1. Go to Overview>Shortcuts.
2. Select Configure Update Rate and follow the instructions.
3. Obtain Network ID and Join Key for the wireless network (available in wireless
Gateway).
4. Select Join Device to Network and follow the instructions.
4.2
Wait for device to join network
1. Go to Overview.
2. Wait for communication status to become Connected.
Note
This takes several minutes. Enable Active Advertising on the Gateway to ensure new
devices are able to join the network faster. For more information see the Emerson Wireless
Gateway
Reference
5.0
Configure k-factor (calibration factor) for pulse
output device or turbine meter
Note
The steps below apply if the k-factor is not preconfigured to the transmitter.
5.1
Primary method
1. Go to Configure>Guided Setup>Basic setup. This will walk you through setting
the device up for first time use.
5.2
Other methods
1. Go to Configure>Manual Setup>Totalizing Options. This is the main interface
for establishing the k-factor as well as other features including low flow cutoff
and manual rollover adjustments.
2. On a HART Handheld, you can configure the k-factor by going to Configure>
Manual Setup>Totalizing Options>Turbine Configuration>k factor.
For more information on these features, see the Rosemount 705
Manual.
10
Manual.
April 2019