Optimising The Stalling Behaviour - Emotron VS10 Operation Instructions Manual

Hide thumbs Also See for VS10:
Table of Contents

Advertisement

7.3.3.

Optimising the stalling behaviour

If the motor is driven with frequencies above the rated motor frequency, the operating
point is shifted to the "field weakening range". In this range, the motor voltage does not
increase proportionately to the output frequency anymore. As a consequence, the
inverter automatically reduces the maximum current since the full torque is not available
anymore at these frequencies.
For special motors which enable an operation in the field weakening range, the behaviour
in the field weakening range can be adapted to the motor with
DANGER!
Danger by incorrect parameterisation.
Possible consequences: damage to material assets and injury to persons
Only change the default setting (0 Hz) in
Recommendation: Maintain default setting (0 Hz).
Preconditions
The function is only effective in the motor control type "V/f characteristic control (VFC
open loop)".
0x2B0C
0x2B0C (P319.00)
after consulting the motor manufacturer!
(P319.00).

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VS10 and is the answer not in the manual?

This manual is also suitable for:

Vs30

Table of Contents

Save PDF