(3) Common specifications of 200 V class and 400 V class models (continued)
Model name (type name)
004
007
L
L/H
SJ700D-****FF3/FEF3/FUF3
Standard
Setting with
operator
External
signal
0 to +10 VDC, -10 to +10 VDC (input impedance: 10k), 4 to 20 mA (input impedance: 100)
(Note6)
External
Setting via RS485 communication
port
Standard
Start/stop commands (forward/reverse switching by parameter setting)
operator
Forward-operation start/stop commands (reverse-operation start/stop possible when relevant commands are assigned to
External
intelligent input terminals)
signal
3-wire input possible (when relevant commands are assigned to control circuit terminals)
External
Setting via RS485 communication
port
8 terminals, NO/NC switchable, sink logic/source logic switchable
[Terminal functions] Select eight of 69 functions.
Reverse operation (RV), Multispeed 1 setting (CF1), Multispeed 2 setting (CF2), Multispeed 3 setting (CF3), Multispeed 4
setting (CF4), Jogging (JG), external DC braking (DB), 2nd motor control (SET), 2-stage acceleration/deceleration (2CH),
free-run stop (FRS), external trip (EXT), unattended start protection (USP), commercial power supply switching (CS),
software lock (SFT), analog input switching (AT), 3rd motor control (SET3), reset (RS), starting by 3-wire input (STA),
stopping by 3-wire input (STP), forward/reverse switching by 3-wire input (F/R), PID disable (PID), PID integration reset
(PIDC), control gain switching (CAS), acceleration by remote control (UP), deceleration by remote control (DWN), data
Intelligent input
clearance by remote control (UDC), forcible operation (OPE), multispeed bit 1 (SF1), multispeed bit 2 (SF2), multispeed
terminals
bit 3 (SF3), multispeed bit 4 (SF4), multispeed bit 5 (SF5), multispeed bit 6 (SF6), multispeed bit 7 (SF7), overload
restriction selection (OLR), torque limit selection (enabling/disabling) (TL), torque limit 1 (TRQ1), torque limit 2 (TRQ2),
P/PI switching (PPI), LAD cancellation (LAC), trigger for frequency addition (A145) (ADD), forcible-terminal
operation (F-TM), cumulative power clearance (KHC), general-purpose input 1 (MI1), general-purpose input 2 (MI2),
general-purpose input 3 (MI3), general-purpose input 4 (MI4), general-purpose input 5 (MI5), general-purpose input 6
(MI6), general-purpose input 7 (MI7), general-purpose input 8 (MI8), analog command holding (AHD), emergency
stop(EMR)*Note4,no assignment (no)
Thermistor input
1 terminal (positive temperature coefficient/negative temperature coefficient switchable for resistor)
terminal
5 open-collector output terminals, NO/NC switchable, sink logic/source logic switchable
1 relay (1c-contact) output terminal: NO/NC switchable
[Terminal functions] Select six of 51 functions.
Running (RUN), constant-speed reached (FA1), set frequency overreached (FA2), overload notice advance signal (1)
(OL), output deviation for PID control (OD), alarm signal (AL), set frequency reached (FA3), over-torque (OTQ),
instantaneous power failure (IP), under voltage (UV), torque limited (TRQ), operation time over (RNT), plug-in time
over (ONT), thermal alarm signal (THM), 0 Hz detection signal (ZS), set frequency overreached 2 (FA4), set frequency
Intelligent
reached 2 (FA5), overload notice advance signal (2) (OL2), PID feedback comparison (FBV), communication line
output terminals
disconnection (NDc), logical operation result 1 (LOG1), logical operation result 2 (LOG2), logical operation result 3
(LOG3), logical operation result 4 (LOG4), logical operation result 5 (LOG5), logical operation result 6 (LOG6),
capacitor life warning (WAC), cooling-fan speed drop (WAF), starting contact signal (FR), heat sink overheat warning
(OHF), low-current indication signal (LOC), general-purpose output 1 (M01), general-purpose output 2 (M02),
general-purpose output 3 (M03), general-purpose output 4 (M04), general-purpose output 5 (M05), general-purpose
output 6 (M06), inverter ready (IRDY), forward rotation (FWR), reverse rotation (RVR), major failure (MJA), alarm code
0 to 3 (AC0 to AC3)
Intelligent
Analog voltage output(Note7), analog current output(Note7), pulse-string output
monitor output
(e.g., A-F, D-F [n-fold, pulse output only], A, T, V, P)
terminals
Monitoring on
Output frequency, output current, output torque, frequency conversion data, trip history,
display
input/output terminal status, electric power, and others
Triggered at motor start-up, when the actual motor frequency exceeds the acceleration frequency set by a stop
DC braking
command, when the actual motor frequency exceeds the frequency set by a frequency command,
or by an externally input command (braking force, time, and frequency are variable).
Free V/f setting (7 breakpoints), frequency upper/lower limit, jump (center) frequency, acceleration/deceleration
according to characteristic curve, manual torque boost level/breakpoint, energy-saving operation, analog meter
adjustment, start frequency setting, carrier frequency adjustment, electronic thermal function (available also for free
Other functions
setting), external start/end frequency/frequency rate, analog input selection, retry after trip, restart after instantaneous
power failure, output of various signals, starting with reduced voltage, overload restriction, initial-value setting, automatic
deceleration at power failure, AVR function, fuzzy acceleration/deceleration, online/offline auto-tuning, high-torque
multi-motor operation (sensorless vector control of two motors by one inverter)
Carrier frequency
variation
Overcurrent protection, overvoltage protection, under voltage protection, electronic thermal protection, temperature error
protection, instantaneous power failure protection,
Protective functions
ground-fault current detection at power-on, USP error, external trip, emergency stop trip, CT error, communication error,
option board error, and others
037
015
022
055
075
040
L/H
L/H
L/H
L/H
L/H
2
2
and
keys
1
1
CT : 0.5 to 15kHz
VT : 0.5 to 12 kHz
110
150
185
220
300
L/H
L/H
L/H
L/H
L/H
input protection, braking-resistor overload protection,
phase loss
6 - 3
Chapter 6 Specifications
370
450
550
750
900
L/H
L/H
L/H
H
H
CT : 0.5 to 10kHz
VT : 0.5 to 8 kHz
1320
1100
1500
H
H