Hitachi SJ700D-3 SERIES Quick Reference Manual page 19

Hide thumbs Also See for SJ700D-3 SERIES:
Table of Contents

Advertisement

Example 4: Frequency command source
Run command source
*) SJ700D-****FEF3/FUF3 (Initial settings)
(1) I/O connections
ELB
*) Refer to S.4.2 for changing the frequency command source and S.4.3 for changing the run
command source.
(2) Operation
Frequency: Using the voltage source and current source to set the frequency command with analog
select terminal (AT terminal: OFF: Voltage command / ON: Current command).
* AT terminal is used to switch the analog input O and OI to which the inverter refers as the
frequency command. (e.g. When AT terminal is OFF, the inverter outputs the frequency
according to the voltage input given to the O terminal)
Run/Stop: Using the forward / reverse terminal to run and stop.
(3) Parameter settings
Parameter
A001
A002
External analog voltage source and current source (Control terminal)
External signal (Control terminal)
PD
N
P
R/L1
S/L2
T/L3
R
T
R0
T0
P24
PLC
CM1
Source logic
Details
Control circuit terminal block
Control circuit terminal block
S - 7
Start-up
Commissioning the drive
3-phase induction motor
RB
U
V
W
V
FW
8:RV
2:AT
P24
PLC
CM1
Sink logic
O
L
OI
M
Forward
Reverse
Analog select
(+)
Voltage source
(-)
(0V to 10V)
(-)
Current source
(4mA to 20mA)
(+)
Setting data



Advertisement

Table of Contents
loading

Table of Contents