Hitachi SJ700D-3 SERIES Quick Reference Manual page 65

Hide thumbs Also See for SJ700D-3 SERIES:
Table of Contents

Advertisement

Code
Function name
b001
Selection of restart mode
b002
Allowable under-voltage power failure time
b003
Retry wait time before motor restart
Instantaneous power failure/under-voltage trip
b004
alarm enable
Number of restarts on power
b005
failure/under-voltage trip events
b006
Input phase loss detection enable
b007
Restart frequency threshold
b008
Selection of retry after tripping
b009
Selection of retry after under voltage
Selection of retry count after overvoltage or
b010
overcurrent
b011
Retry wait time after tripping
b012
Electronic thermal setting
b212
Electronic thermal setting , 2nd motor
b312
Electronic thermal setting, 3rd motor
b013 Electronic thermal characteristic
b213 Electronic thermal characteristic, 2nd motor
b313 Electronic thermal characteristic, 3rd motor
b015
Free setting, electronic thermal frequency (1)
b016
Free setting, electronic thermal current (1)
b017
Free setting, electronic thermal frequency (2)
b018
Free setting, electronic thermal current (2)
b019
Free setting, electronic thermal frequency (3)
b020
Free setting, electronic thermal current (3)
b021
Overload restriction operation mode
b022
Overload restriction setting
b023
Deceleration rate at overload restriction
b024
Overload restriction operation mode (2)
b025
Overload restriction setting (2)
b026
Deceleration rate at overload restriction (2)
b027
Overcurrent suppression enable
b028
Active frequency matching, scan start frequency
b029
Active frequency matching, scan-time constant
Active frequency matching, restart frequency
b030
select
b031
Software lock mode selection
(Note) < >indicate the setting range of 75 to 150kW
(Note) CT : Constant torque mode, VT : Variable torque mode, you can set CT or VT by b049.
Monitored data or setting
00 (tripping), 01 (starting with 0 Hz),
02 (starting with matching frequency),
03 (tripping after deceleration and stopping with matching
frequency), 04 (restarting with active matching frequency)
0.3 to 25.0 (s)
0.3 to 100.0 (s)
00 (disabling), 01 (enabling),
02 (disabling during stopping and decelerating to stop)
00 (16 times), 01 (unlimited)
00 (disabling), 01 (enabling)
0.00 to 99.99, 100.0 to 400.0 (Hz)
00 (tripping), 01 (starting with 0 Hz),
02 (starting with matching frequency),
03 (tripping after deceleration and stopping with matching
frequency), 04 (restarting with active matching frequency)
00 (16 times), 01 (unlimited)
1 to 3 (times)
0.3 to 100.0 (s)
0.20 x "rated current" to 1.00 x "rated current" (A)
00 (reduced-torque characteristic),
01 (constant-torque characteristic),
02 (free setting)
0. to 400. (Hz)
0.0 to rated current (A)
0. to 400. (Hz)
0.0 to rated current (A)
0. to 400. (Hz)
0.0 to rated current (A)
00 (disabling), 01 (enabling during acceleration and deceleration),
02 (enabling during constant speed),
03 (enabling during acceleration and deceleration (increasing the
speed during regeneration))
0.20 x "rated current" to 2.00 x "rated current" (A)
<0.20 x "rated current" to1.80 x "rated current" (A)>
(In case of CT)
0.20 x "rated current" to 1.50 x "rated current" (A)
(In case of VT)
0.10 to 30.00 (s)
00 (disabling), 01 (enabling during acceleration and deceleration),
02 (enabling during constant speed),
03 (enabling during acceleration and deceleration (increasing the
speed during regeneration))
0.20 x "rated current" to 1.50 x "rated current" (A)
<0.20 x "rated current" to1.50 x "rated current" (A)>
0.10 to 30.00 (s)
00 (disabling), 01 (enabling)
0.20 x "rated current" to 2.00 x "rated current" (A)
<0.20 x "rated current" to1.80 x "rated current" (A)>
(In case of CT)
0.20 x "rated current" to 1.50 x "rated current" (A)
(In case of VT)
0.10 to 30.00 (s)
00 (frequency at the last shutoff),
01 (maximum frequency), 02 (set frequency)
00 (disabling change of data other than "b031" when SFT is on),
01 (disabling change of data other than "b031" and frequency
settings when SFT is on),
02 (disabling change of data other than "b031"),
03 (disabling change of data other than "b031" and frequency
settings),
10 (enabling data changes during operation)
4 - 7
Chapter 4
List of Data Settings
FF FEF FUF
Rated current
Rated current
Rated current
00
00
00
Rated current
x 1.50 (CT)
Rated current
x1.20 (VT)
Rated current
x 1.50 (CT)
Rated current
x1.20 (VT)
Rated current
Change during
Default
RUN operation
b031≠10
b031=10
00
Not
Allowed
1.0
Not
Allowed
1.0
Not
Allowed
00
Not
Allowed
00
Not
Allowed
00
Not
Allowed
0.00
Not
Allowed
00
Not
Allowed
00
Not
Allowed
3
Not
Allowed
1.0
Not
Allowed
Not
Allowed
Not
Allowed
Not
Allowed
01 01
Not
Allowed
01 01
Not
Allowed
01 01
Not
Allowed
0.
Not
Allowed
0.0
Not
Allowed
0.
Not
Allowed
0.0
Not
Allowed
0.
Not
Allowed
0.0
Not
Allowed
01
Not
Allowed
Not
Allowed
1.00
Not
Allowed
01
Not
Allowed
Not
Allowed
1.00
Not
Allowed
01
Not
Allowed
Not
Allowed
0.50
Not
Allowed
00
Not
Allowed
01
Not
Allowed