Hitachi SJ700D-3 SERIES Quick Reference Manual page 7

Hide thumbs Also See for SJ700D-3 SERIES:
Table of Contents

Advertisement

Cautions for UL and cUL (0.4kW-150kW)
(Standard to comply with: UL508C, CSA C22.2 No14-5)
Warning Markings
GENERAL:
These devices are open type and/or Enclosed Type 1 (when employing accessory Type 1 Chassis Kit) AC Inverters
with three phase input and three phase output. They are intended to be used in an enclosure. They are used to
provide both an adjustable voltage and adjustable frequency to the ac motor. The inverter automatically maintains
the required volts-Hz ration allowing the capability through the motor speed range.
"Use 60/75C CU wire only" or equivalent.
(1)
For models SJ700D series except for models SJ700D-055H, SJ700D-075H, SJ700D-110H.
"Use 75C CU wire only" or equivalent.
(2)
For models SJ700D series except for SJ700D-075H, SJ700D-110H, SJ700D-055H.
"Suitable for use on a circuit capable of delivering not more than 100,000rms symmetrical amperes,
(3)
240V maximum". For models with suffix L.
"Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes,
(4)
480V maximum". For models with suffix H.
"Install device in pollution degree 2 environment"
(5)
"Maximum Surrounding Air Temperature 45 or 50C"
(6)
"CAUTION - Risk of Electric Shock - Capacitor discharge time is at least 10 min."
(7)
"Integral solid state short circuit protection does not provide branch circuit protection.
(8)
Branch circuit protection must be provided in accordance with the NEC and any additional local codes"
"Solid State motor overload protection reacts with max. 120% of FLA".
(9)
(10) Tightening torque and wire range for field wiring terminals are in the table below:
Model No.
Required Torque (N.m)
SJ700D-004L
SJ700D-007L
SJ700D-015L
SJ700D-022L
SJ700D-037L
SJ700D-050L
SJ700D-055L
SJ700D-075L
SJ700D-110L
SJ700D-150L
SJ700D-185L
SJ700D-220L
SJ700D-300L
SJ700D-370L
SJ700D-450L
SJ700D-550L
1.8
1.8
1.8
1.8
1.8
3.0
4.0
4.0
4.0
4.9
4.9
8.8
8.8
20.0
20.0
19.6
(Prepared wire only) or Parallel of 2/0 (Prepared wire only)
Wire Range (AWG)
14(Stranded only)
14(Stranded only)
14(Stranded only)
14(Stranded only)
10(Stranded only)
8
8
6
6-4
2
1
1 or 1/0
2/0 or Parallel of 1/0
4/0 (Prepared wire only) or Parallel of 1/0
4/0 (Prepared wire only) or Parallel of 1/0
350 kcmil
v
Safety Instructions