Flue temperature:
▶ To prevent the risk of flue material overheat the appliance's
flue temperature is sensed and is limited. The flue
temperature limit is depending on inlet water temperature.
▶ Residential models: Maximum flue temperature is limited
to 145 °F (63 °C).
4.6.1 Vent options
This appliance can be installed as direct vent or Category IV.
The Greentherm T9900 SE/i is approved with the following
venting options:
Item
Vent or air intake pipe
and fitting
Pipe cement / primer
Table 5
Approved vent materials
For specific questions concerning vent material,
specifications, usage or installation, please contact the
vent manufacturer directly.
Approved Vent Manufacturers;
•
M&G
•
Centrotherm
•
IPEX
•
Royal Plastics
•
Eccovent
•
Charlotte
•
Z-Flex
Do not use cellular foam core pipe for exhaust.This material is
approved for intake only.
The vent connection for the appliance is secured with a clamp
on the appliance exhaust adapter. All other vent connections
must be glued, except PP and flex PP. Slide the vent pipe into
Greentherm T9900 SE/i – 6 720 813 635 (2019/03)
Material
PP
flexible
concentric
rigid
PVC
schedule 40
PVC-DWV
CPVC
schedule 40
ABS-DWV
schedule 40
PVC
CPVC
ABS
United States
M&G /
DuraventCentrotherm
ANSI/ASTM D1785
ANSI/ASTM D2665
ANSI/ASTM F441
ANSI/ASTM D2661
ANSI/ASTM D2564
ANSI/ASTM F493
ANSI/ASTM D2235
the exhaust adapter. The exhaust pipe must be properly
supported and must be pitched a minimum of a ¼ inch per foot
back to the appliance. This allows the condensate to drain
properly.
Maximum vent lengths and equivalent lengths per table 8
apply.
Installation instructions
Canada
Thermoplastic vent pipe
must be certified to ULC
S636.
Air Intake pipe may be of any
material listed (left)