Time and Date Settings
The internal clock of the control system can be configured using console
commands.
1.
2. Issue the timezone command to set the time zone:
3. Issue the SNTP START command to synchronize the internal clock with an
The internal clock can also be set using the System Clock function in Crestron
Toolbox. For more information, refer to the Crestron Toolbox help file.
Reference Guide – DOC. 7150B
Issue the timedate command to manually set the time and date.
Syntax: timedate [hh:mm:ss mm-dd-yyyy]
•
For hh:mm:ss, enter the time in hours (using 24-hour format),
o
minutes, and seconds format.
For mm-dd-yyyy (or mm/dd/yyyy), enter the date in month (1–12),
o
day (1–31), and year format.
Example: timedate 12:18:30 03-14-2019
•
Syntax: timezone [LIST | zone]
•
For zone, enter the three-digit code for the time zone.
o
Use the LIST parameter to print a list of all time zones and their
o
codes in the console.
Example: timezone 014
•
SNTP server:
Syntax: SNTP START [SERVER:address] [PERIOD:time]
•
For SERVER, enter the address (in dot decimal notation) of the
o
SNTP server.
For PERIOD, enter the interval (in minutes, minimum is 10) that the
o
internal clock synchronizes with the SNTP server.
Example: SNTP START SERVER:255.255.255.255 PERIOD:60
•
3-Series Control Systems • 9