Common Fault. Red LED flashes slowly when a single
or multiple common fault #1 occurs. Yellow LED flashes
slowly when a single or multiple common fault #2
occurs. User Programmed Inputs #1 through #5 can be
assigned to indicate a common fault and are discussed
later in this section. See also Figure 7.
Controller
Master RSA III
Slave RSA(s)
APM802
Decision-Makerr 3+
Decision-Makerr 550
Decision-Makerr 3000
Decision-Makerr 3500
Decision-Makerr 6000
Decision-Makerr 8000
KPC 1000
MPACr 750
MPACr 1000
MPACr 1200
MPACr 1500
Figure 7 RSA III User Defined Inputs and EPS
Supplying Load Defaults
Common faults are selectable on the DEC 550
controller using the respective controller menu choices.
The 550 controller offers two choices for common fault
setup.
Configure a programmable digital output on the
D
DEC 550 as a common fault and wire that into one of
the DEC 550's programmable user inputs 7, 8, or 10.
Use SiteTecht to configure the corresponding RSA
user input source 1, 2, or 3 (P41-2, -4, or -6). This is
the recommended approach since another line from
the DEC 550 to the RSA is unnecessary.
Configure a programmable digital output on the
D
DEC 550 as a common fault and wire that into the
RSA's user input source 1, 2, or 3 (P41-2, -4, or -6).
Modbusr is a registered trademark of Schneider Electric.
6
Assignment
Digital input
method
count
Automatic
5
Not applicable
Not accessible
Via SiteTecht
16
3
Via SiteTecht
Via SiteTecht
32
Via SiteTecht
3
Via SiteTecht
6
Via SiteTecht
32
Via SiteTecht
8
Not applicable
0
2
Via SiteTecht
Via SiteTecht
2
2
Via SiteTecht
Via SiteTecht
2
The DEC 3+ controller offers two choices for common
faults using terminal 32 or 32A.
Terminal 32 on the DEC 3+ provides the following ten
common faults:
Auxiliary Warning
D
(Generator Switch) Not-In-Auto
D
High Engine Temperature Shutdown
D
High Engine Temperature Warning
D
Low Water Temperature Warning
D
Low Fuel Warning
D
Low Oil Pressure Shutdown
D
Low Oil Pressure Warning
D
Overcrank Shutdown
D
Overspeed Shutdown
D
Terminal 32A on the DEC 3+ provides the following five
common faults:
Auxiliary Warning
D
Emergency Stop
D
High Engine Temperature Shutdown
D
Low Oil Pressure Shutdown
D
Overspeed Shutdown
D
Communication Status. The RSA III is shipped from
the
factory
preset
communicating with a generator set controller on
Modbusr address #1 and/or ATS controller on Modbusr
address #2 with ATS connected set to False. The
generator set controller is a slave device. Additional
RSA III devices on the same network must be reset in
the field as slave devices. See Figure 6 and Figure 8.
LED
LED Status
Horn Function
Green Steady on
Off
Green Flashes slow Off
Green Flashes fast
Off
Red
Flashes fast
On
Red
Flashes slow On
Red
Steady on
On
Figure 8 Communication Status
Note: Should any communication issues occur when
adding RSA III slaves and/or transfer switches to
the system, be sure to power down the RSA III
master and then power up the RSA III master so
that the RSA III master can recognize the
changes.
as
a
master
device
Communication is okay
When communication is being
established
When the master RSA II
communication configuration does
not match the device
When the master RSA II
encounters a communication
problem with a device
When the slave RSA II does not
detect the master RSA II
When the master RSA II is set up
to communicate with the slave
RSA II and the slave RSA II does
not respond to the master RSA II
TT-1625 7/17