Select A Mounting Location For The Unit; Communication Module Tb5 Terminal Strip Connections; Wire Specifications For Communication Module Connections - Kohler APM802 Installation Instructions Manual

Table of Contents

Advertisement

Connector Designation
1
2
3
4
5
6
7
8
9
10
11
12
* Reserved for high battery volts (HBV) on DEC 3+ controllers.
Figure 12 Communication Module TB5 Terminal Strip
Connections
4.5
Connect wiring from the user-supplied battery
charger high battery voltage contacts to the
remaining terminal on harness GM35318 and
TB5-6 for RSA III annunciation of (high) Battery
Voltage. See Figure 13 for wire sizes.
Length, m (ft.)
0--137
(0--450)
137--213
(450--700)
213--343
(700--1125)
343--549
(1125--1800)
549--853
(1800--2800)
Figure 13 Wire Specifications for Communication
Module Connections
4.6
EPS Supplying Load. Connect wiring from the
user-supplied transfer switch (ATS) emergency
position auxiliary contacts to terminals TB5-3 and
TB5-9 for RSA III annunciation of EPS Supplying
Load. See Figure 13 for wire sizes.
4.7
User Input 1 and User Input 2. Make additional
user-selected connections to the communication
module board TB5 terminal block. See Figure 13
for wire sizes. The user-selected connections
are defined in Figure 12 and include:
User Input 1 (remote).
D
User Input 2 (remote).
D
Note: User input 3 is reserved for high battery
voltage as outlined in step 4.4.
TT-1625 7/17
Circuit Board Designation
Not used
Not used
ATS Position Input Return
User 1 Input Return
User 2 Input Return
User 3 Input Return *
Not used
Not used
ATS Position Input
User 1 Input
User 2 Input
User 3 Input *
Wire Gauge
22
20
18
16
14
Document the user-selected inputs for future
reference. If user-selected inputs 1--2 (remote)
are used, the user may add the identification on
the RSA III front panel strip. This procedure is
further explained in step 6.13 of this instruction.
5.
Select a mounting location for the
RSA III.
Note: Use step 5 for mounting the RSA III master and
the RSA III slaves as needed. Connect up to
three RSA III slaves maximum.
wiring information is covered in step 6.
5.1
Select a visible location for mounting the RSA III
up to 853 m (2800 ft.) from the controller. Install
the RSA III, either surface- or flush-mounted, in a
location
easily
personnel at their work stations. See Figure 14
for RSA III overall dimensions.
Figure 15 and Figure 16 for the dimension prints.
Note: Locate all RSA III within 853 m (2800 ft.) of
the controller.
W
H
TT-1625-
Surface Mounted
Dimensions—W x H x D, mm (in.)
Surface Mounted: 203 x 203 x 76.2 (8.0 x 8.0 x 3.0)
Flush Mounted:
203 x 203 x 76.2 (8.0 x 8.0 x 3.0)
Flush-mounting plate W1: 254 (10.0)
Flush Mounted*: 203 x 203 x 103 (8.0 x 8.0 x 4.1)
Flush-mounting plate W1: 254 (10.0)
* Requires user-supplied Hoffman box 203 x 203 x 102 mm (8 x 8 x 4 in.)
Figure 14 RSA III Box Dimensions
The RSA III
observable
by
operating
Refer to
W
D
W1
D
Flush Mounted
H
13