Mounting; Safety Precautions; User Programmed Inputs #1 To #5; Disabling The Generator Set - Kohler APM802 Installation Instructions Manual

Table of Contents

Advertisement

User Programmed Inputs #1 to #5. Monitors five
digital inputs (status, warnings, added user inputs
and/or shutdowns). Use the SiteTecht software to
select the desired user input and assign a severity level
(warning or shutdown fault). A separate yellow or red
LED flashes for each input when a respective warning or
shutdown fault occurs or the status changes. See
Figure 7.
Note: If in SiteTecht the user attempts to assign a
digital input outside of the range for the controller
or ATS, an error message will be displayed by
SiteTecht and the Common Fault LED and
associated User Input LED will flash.
The five user input LEDs automatically correspond to
the on-board terminal blocks labeled USER 1 to 5, in
order of their numeric designators (LED1 to Input1 etc.),
unless altered using SiteTecht. Any digital input from
the Kohler generator controllers and ATS can be
associated with any of the five user input LEDs.
User-defined digital inputs #1 through #5 are selected at
the RSA III master only using SiteTecht software and
annunciated to the RSA III slave(s). No user-defined
digital input selection is available at the RSA III slave(s).
User-defined digital inputs tied directly to the RSA III
master are considered local. User-defined digital inputs
connected to the controller are considered remote.
Note: Although all digital inputs are selectable on the
RSA III, some digital inputs have assigned
functions. Check the generator set configuration
to determine input availability.
DEC 3+ Controller. User-defined digital input #3 is
D
also used for high battery voltage and requires
battery charger with alarms.
DEC 550, DEC 3000, DEC 3500, and DEC 6000
D
Controllers. User-defined digital inputs tied directly
to the RSA III master are considered local.
DEC 8000 and APM802 Controllers. User-defined
D
inputs tied to controller terminal block are considered
remote.
Figure 6 shows the status of the system ready LED,
generator running LED, communication status LED,
common fault LED, common fault output, and horn for
each fault or status condition.

Mounting

Surface Mounting or Flush Mounting capability is
standard.
This document includes installation information for both
surface- and flush-mount models.
8

Safety Precautions

Observe the following safety precautions while
installing the kit.
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working
on
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.

Disabling the generator set.

cause severe injury or death.
generator set or equipment connected to the set, disable the
generator set as follows: (1) Shut down the generator set. (2)
Place the controller in Out of Service mode. (3) Press the
emergency stop button. (4) Disconnect the power to the
battery charger, if equipped. (5) Remove the battery cables,
negative (--) lead first. Reconnect the negative (--) lead last
when reconnecting the battery. Follow these precautions to
prevent the starting of the generator set by the remote
start/stop switch.
(APM802 Controller)
Disabling the generator set.
cause severe injury or death.
generator set or equipment connected to the set, disable the
generator set as follows: (1) Move the generator set master
switch to the OFF position. (2) Disconnect the power to the
battery charger. (3) Remove the battery cables, negative (--)
lead first.
Reconnect the negative (--) lead last when
reconnecting the battery. Follow these precautions to prevent
starting of the generator set by an automatic transfer switch,
remote start/stop switch, or engine start command from a
remote computer.
(Decision-Makerr 3+ and 550 Controllers)
Disabling the generator set.
cause severe injury or death.
generator set or equipment connected to the set, disable the
generator set as follows: (1) Press the generator set off/reset
button to shut down the generator set. (2) Disconnect the
power to the battery charger, if equipped. (3) Remove the
battery cables, negative (--) lead first. Reconnect the negative
(--) lead last when reconnecting the battery. Follow these
precautions to prevent the starting of the generator set by the
remote start/stop switch.
(Decision-Makerr 3000, 3500, and 6000 Controllers)
the
generator
set.
Accidental starting can
Before working on the
Accidental starting can
Before working on the
Accidental starting can
Before working on the
TT-1625 7/17