P41, 8-pin input (EPS/user) connections. See
Figure 20 for location of P41 on the RSA III. See
Figure 41 for P41 User Input 1--3 Connections.
See Figure 42 for P42 User Input 4--5
Connections
(Decision-Makerr 3500 controllers
only).
P41 Input/Connections
P41-1
Local ATS emergency on input *
P41-2
Local ATS emergency on input return *
P41-3
User input 1
P41-4
User input 1 return
P41-5
User Input 2
P41-6
User Input 2 return
P41-7
User Input 3
P41-8
User Input 3 return
* Applies to Decision-Makerr 3+ controller only. Supplied via
Modbusr RS-485 on the Decision-Makerr 550, 3000, 3500
controllers.
Figure 41 RSA P41User Input 1--3 Connections
P42 Connections
P42-1
User input 4
P42-2
User input 4 return
P42-3
User input 5
P42-4
User input 5 return
Figure 42 RSA P42 User Input 4--5 Connections
Controller
User Input 1
Master RSA III
P41-3 user-
(Local)
selectable
TB5-10 on
comm. module,
DEC 3+
user- selectable
TB4-7 (D7)
DEC 550
user-selectable
using Menu 9
DEC 3000
TB1-DI 1
DEC 3500
TB1-DI 1
TB4-7 (D7)
user-selectable
DEC 6000
using Menu 9
MPACr 750
MPACr 1000
Main logic board input #1
MPACr 1200
MPACr 1500
Figure 44 RSA III Local P41 Input Connections
26
User Input 2
P41-4
P41-5 user-
(ground)
selectable
TB5-11 on
TB5-4
comm. module,
(ground)
user- selectable
TB4-8 (D8)
TB4-28
user-selectable
(ground)
using Menu 9
TB1-GND
TB1-DI 2
or ground
TB1-GND
TB1-DI 2
or ground
TB4-8 (D8)
TB4-28
user-selectable
(ground)
using Menu 9
Main logic board input #2
6.9
Make
any
connections to the RSA III P41 connector. User-
defined inputs can be used for any status,
warning, or shutdown including open circuit
breaker, air damper, etc.
connections are defined in Figure 43 and
Figure 44 and include:
User Input 1 (local).
D
User Input 2 (local).
D
User Input 3 (local).
D
User Input 4 (local).
D
User Input 5 (local).
D
ATS emergency input (local). Connect wiring
D
from the user-supplied transfer switch (ATS)
emergency position auxiliary contacts. See the
respective ATS wiring diagram(s).
Note: User-defined digital inputs #1 to #5 are
selected at the RSA III master only and
annunciated to the RSA III slave(s). No
user-defined digital input selection is
available at the RSA III slave(s).
Controller
User Input 4
Master RSA
P42-1 user-
III (Local)
selectable
DEC 3500
TB1-DI 4
Figure 43 RSA III Local P42 Input Connections
User Input 3
P41-6
P41-7 user-
(ground)
selectable
TB5-12 on
comm. module,
TB5-5
user- selectable
(ground)
Also used for high battery
voltage on comm. module
TB4-10 (D10)
TB4-29
user-selectable
(ground)
using Menu 9
TB1-GND
TB1-DI 3
or ground
TB1-GND
TB1-DI 3
or ground
TB4-10 (D10)
TB4-29
user-selectable
(ground)
using Menu 9
additional
local
user-selected
The user-selection
User Input 5
P42-2
P42-3 user-
(ground)
selectable
TB1-GND
TB1-DI 5
or ground
ATS Emergency Aux. Contacts
for EPS Supplying Load Input
P41-8
P41-1 on
P41-2 (ground)
(ground)
RSA III
on RSA III
TB5-9 on
TB5-3 on
TB5-6
comm. module
comm. module
(ground)
and then to
and then to
P41-8 on
P41-7 (ground)
RSA III
on RSA III
TB4-31
via RS-485
via RS-485
(ground)
TB1-GND
via RS-485
via RS-485
or ground
TB1-GND
via RS-485
via RS-485
or ground
TB4-31
via RS-485
via RS-485
(ground)
via RS-485
via RS-485
P42-4
(ground)
TB1-GND
or ground
TT-1625 7/17