Download Print this page

GE VAT300 Series Quick Manual page 17

Power protection

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 3
1) Control terminal TB1,TB2
・The terminal block is laid out in two rows.
・Terminal screw size is M3.
2) Dip switches DS1
No.
OFF
1
OPEN
2
V1
3
V2
4
PS03
3) EL-BIT W1,W2,W3,W4
No.
W1
SINK
W2
SINK
W3
voltage
W4
voltage
4) Standard serial or Modbus transmission
CN2 (Connector type: 4-pole modular, Hirose Electric TM3P-44P or equivalent)
・A signal level is based RS-485. The terminus resistance (120Ω) can set up on/off in DS1-1.
((DS1-1=120Ω): Connected, (DS1-1=OPEN): Not connected)
・The direction of a signal is based on VAT300.
・5VOP and 0VOP are not designed to supply power to any external devices.
Terminal
No.
1
DATA+
2
3
4
5) Standard serial or Modbus transmission TB3
・CN2 and TB3 DATA+, DATA- and 0VOP are connected in the PCB.
・The terminal size is M2.
・The applicable wire size is AWG26 to AWG16.
Terminal
Symbol
No.
1
D+
2
D-
3
SG
ON
Standard serial terminator changeover
120Ω
I1
AI1 voltage, current changeover
I2
AI2 voltage, current changeover
PULSE
Sequence output, pulse train output changeover
SOURCE PSI1~6 sink,source changeovers
SOURCE PSI7 sink,source changeover
current
AO1 voltage, current changeover
current
AO2 voltage, current changeover
Signal
DATA-
0VOP
5VOP
Signal
DATA+
DATA-
0VOP
EN-15
Signal
Signal
5mm
6.6mm
Outline drawing of connector
Wire peeling size
5mm
All switches are
set to OFF as the
default.
All EL-BITs are
set to 1 as the
default.
4
3
2
1
7.7mm

Advertisement