Model 5600 Installation and Operation Manual
5.5

Addressing SLC Devices

All HFS/SK devices are addressed using the two rotary dials that appear on the device board.
Use the ONES rotary dial to set the ones place in a one or two digit number, and use the TENS
rotary dial to set the tens place in a two digit number.
Example 1: To select device address 35, turn the ONES rotary dial to 5 and the TENS rotary
dial to 3 as shown in Figure 5-4.
Example 2: To select device address 105, turn the ONES rotary dial to 5 and the TENS rotary
dial to 10 as show in Figure 5-4.
All dials labeled for ONES
or TENS position
Example 1: Device Set to 35
Figure 5-4 HFS/SK SLC Device Addressing Using Rotary Dials
5-6
Example 2: Device set to 105
151450