Electrical Specifications

Table 3-1 list the electrical specifications for the 5600 field wiring as well as a description of
the each individual terminal and their respective electrical rating. For location of the terminals
refer to 3.5. See also Section 4 for installation.
Label
Terminal
Block
Group
Individual
TB 1
SBUS
+
A
B
SLC Out
+
*NAC1
+
*NAC2
+
TROUBLE NO
COM
NC
RELAY 1
NO
COM
NC
RELAY 2
NO
COM
NC
TB 2
TELCO 1
RING
TIP
PHONE 1
RING
TIP
TELCO 2
RING
TIP
PHONE 2
RING
TIP
*
Regulated for NAC circuits
*
Special application when used for auxiliary power circuits.
3-2
Table 3-1: Terminal Descriptions
Description
SBUS Power
SBUS Communication
SLC Terminals
Notification Appliance Circuit 24 VDC
Auxiliary power
Notification Appliance Circuit 24 VDC
Auxiliary power
Normally open relay contact
Common terminal
Normally closed relay contact
Normally open relay contact
Common terminal
Normally closed relay contact
Normally open relay contact
Common terminal
Normally closed relay contact
Phone Line 1 Telco Ring
Phone Line 1 Telco Tip
Phone Line 1 Phone Ring
Phone Line 1 Phone Tip
Phone Line 2 Telco Ring
Phone Line 2 Telco Tip
Phone Line 2 Phone Ring
Phone Line 2 Phone Tip
Rating
Voltage
Current
27.4 VDC
100 mA
3.3 VDC
10 mA
24 VDC
100 mA
2.0 Amp
1.0 Amp
2.0 Amp
1.0 Amp
24 VDC
2.5 A, resistive
24 VDC
2.5 A, resistive
24 VDC
2.5 A, resistive
N/A
N/A
Earth Ground
Fault Impedance
Ohms
N/A
N/A
N/A
N/A
151450