7.6

Viewing Active Supervisory Points

When one or more SLC points within a zone are in supervisory alarm, the supervisory LED
for that zone will blink and outputs will activate that are mapped to supervisories within the
zone. To display the SLC address of an input point that is in supervisory, press the SUPERVS
ID key once and use the PREV (previous) or NEXT key to scroll through the supervisory
points. All points that are in supervisory spanning all zones on the control panel will be
displayed when using the scroll keys.
7.7

Viewing Active Trouble Points

When one or more SLC points within a zone are in trouble, the trouble LED for that zone will
blink and outputs will activate that are mapped to troubles within the zone. To display the SLC
address of an input point that is in trouble, press the TROUBLE ID key once and use the
PREV (previous) or NEXT key to scroll through the trouble points. All addressable points that
are in trouble throughout the control panel will be displayed when using the scroll keys.
Note: If there are any system level troubles active, the LED corresponding to the system level trouble will blink
also. However, system level troubles are not displayed on the 7 segment display after using the TROUBLE
ID key and the PREV or NEXT to scroll addressable troubles. Only point troubles are displayed.
7.8

Walk Test

Walk test is enabled by holding the WALK TEST key until the PZT stops. This takes about 5
seconds. Once in walk test the 7 segment display will show that the walk test is active. During
walk test, inputs can be activated and the outputs that are mapped to the input will be activated
for 3 seconds. The input will automatically be reset when the outputs are deactivated.
The exit walk test, hold the WALK TEST key until the PZT stops. The panel is now in normal
standby mode.
7.9

Fire Drill

A fire drill is activated by holding the DRILL key until the 7 segment display shows drl on.
All outputs will be active. To stop the fire drill, press the RESET key. If the reset key is not
pressed within 10 minutes, the fire drill will automatically reset.