6.6.7

Dialer Account programming Options

Up to two accounts can be used for reporting events to the central station. A typical reason to
use multiple reporting accounts might be to have one account for reporting alarms and a
different account for reporting supervisories and troubles. The programming options for each
account are described below.

6.6.7.1 Account Number

Up to six digits allowed for SIA formats or up to four digits for contact ID format. Default
account numbers are blank.

6.6.7.2 Phone Number

Enter the phone number to call the central station. Default setting is blank.
The following special characters are available:
#
*
,

6.6.7.3 Reporting Format

Choose SIA8 (up to 8 events per call), SIA20 (up to 20 events per call) or contact ID reporting
format. Default setting is contact ID.

6.6.7.4 Reporting Filters

Selecting the Must option forces the event type to be reported to the account even if it was
already reported to another account. Selecting the Yes option will insure that the event type
gets to at least one account. Selecting the No option means that the event type will not be
reported to this account. The default setting is No.
Selecting No for all report filters in both accounts effectively disables the dialer.
6-12
Table 6-4:: Special Dialing Characters
Pound (or number) key on the telephone
Star key on the telephone
Comma (character for 2-second pause)
151450