Download Print this page
Honeywell Silent Knight 5860 Product Installation Document

Honeywell Silent Knight 5860 Product Installation Document

Remote fire annunciator

Advertisement

Quick Links

5860/5860R
Remote Fire Annunciator
Product Installation Document
1 Description
The 5860 (gray) and 5860R (red) are optional 4x20 remote annunciators
that can be surface or flush-mounted.
Figure 1 5860/R Remote Annunciator
2 Compatibility
The 5860/R is compatible with Honeywell Silent Knight FACPs. For
more information, see the FACP Installation manual.
Document 151042:E
2/15/2022
FIRE ALARM ANNUNCIATOR
ECN: 151062
3 Specifications
Parameter
Operating Voltage:
Current
Standby:
Alarm:
Operating Temperature:
backbox
6.44"
(16.35cm)
1
.25
"
8
.125
" (20.64cm)
(3.175cm)
Figure 2 Annunciator Dimensions
4 Installing the 5860/R
5860/R installation involves the following steps:
1.
Ensure power is turned off at the panel.
2.
Mount the 5860/R in the desired location.
3.
Connect the 5860/R to the panel (see Figure 5).
4.
Use the DIP switches on the back of the 5860/R to assign an ID
number. See the FACP Manual for more details.
5.
The new 5860/R module must be added to the system through
programming. The JumpStart
the module automatically. Refer to the FACP Manual for more
information.
5 Mounting
The 5860/R comes from the factory fully assembled. You must disas-
semble it for mounting. To disassemble the annunciator, use a 5/64" hex
wrench to remove the set screws, located on the bottom of the annuncia-
tor bezel.
Value
24 VDC
58 mA
68 mA
0° to 49° C (32° to 120° F)
bezel
7
.375
"
(18.73cm)
®
Auto-programming feature will add
side
view
1
.25
"
(3.175cm)

Advertisement

loading

Summary of Contents for Honeywell Silent Knight 5860

  • Page 1 ” (3.175cm) 2 Compatibility Figure 2 Annunciator Dimensions The 5860/R is compatible with Honeywell Silent Knight FACPs. For more information, see the FACP Installation manual. 4 Installing the 5860/R 5860/R installation involves the following steps: Ensure power is turned off at the panel.
  • Page 2 5.1 Surface Mounting 5.2.1 Flush-Mounting with an Electrical Box The 5860/R can be mounted directly to a surface or can be attached to a The 5860/R annunciator can be used with the following types of electri- single, double, or four-square electrical box. Trim Ring Kit 5860TG cal boxes: 4S, single-gang, and double-gang.