Hitachi HIDIC EH-150 Applications Manual page 102

Programable controller; ethernet module(eh-eth)
Hide thumbs Also See for HIDIC EH-150:
Table of Contents

Advertisement

(2) Various kinds setting
Various kinds setting start
DIP SW bit 1 is ON,
Bit 2 is OFF.
DIP SW bit 3 to 8 are
There is response of
ping command
Display setup page
By Web browser
Abnormal setting
Complete of various kinds setting
Y
all OFF.
N
Y
Y
N
10-2
Chapter 10 Troubleshooting
Some parameters can be changed
N
only with the dip switch
configuration shown as left.
This DIP SW configuration is not
allowed to use.
Y
The bit 3 to 8 is for the lowest byte
of IP address.
The network is not on line
physically or logically. Check the
below items.
- Communication cable and HUB
etc.
N
- Wrong IP address in the host
computer.
- Duplication of IP address to
other stations.
Proxy setting of your Web browser
N
may be wrong. Check if "use
proxy server".
Set up an appropriate value
Y
according to the error message.