Fuse Switch Disconnector (Input Current ≤ 800 A); Circuit Breaker (Input Current > 800 A) - Siemens SINAMICS S120 Equipment Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

5.1.2.1
Fuse switch disconnector (input current ≤ 800 A)
Up to 800 A, a switch disconnector with integrated fuses is incorporated.
Terminal block -X50 – "Fuse switch disconnector" checkback contact
Table 5- 2
Terminal
1
2
3
1)
5.1.2.2
Circuit breaker (input current > 800 A)
At currents greater than 800 A, the circuit breaker, which is located in the center of the
cabinet, takes on the function of isolating the system from the supply and the overload and
short-circuit protection. The circuit breaker is internally activated and has its own internal
power supply.
The tripping current on the line-side must be set according to the conditions of the system.
The tripping current is set as follows in the default factory setting:
Table 5- 3
Factory setting of the overcurrent release on Line Connection Modules for Active Line Modules
Order number
Line Connection
Module
6SL3700-0LE41-0AA0
6SL3700-0LE41-3AA0
6SL3700-0LE41-6AA0
6SL3700-0LE42-0BA0
6SL3700-0LE43-2BA0
6SL3700-0LG41-3AA0
6SL3700-0LG41-6AA0
6SL3700-0LG42-0BA0
6SL3700-0LG42-0BA0
6SL3700-0LG42-5BA0
S120 Cabinet Modules Equipment Manual
Manual, (GH5), 10/2008, A5E00427098A
Terminal block -X50 – "Fuse switch disconnector" checkback contact
Designation
1)
NO
NC
COM
NC: normally-closed contact, NO: normally-open contact, COM: mid-position contact,
max. connectable cross section: 2.5 mm²
Order number
Active Line Module
6SL3730-7TE38-4BA0
6SL3730-7TE41-0BA0
6SL3730-7TE41-4BA0
6SL3730-7TE41-0B_0
6SL3730-7TE41-4B_0
6SL3730-7TG41-0BA0
6SL3730-7TG41-3BA0
6SL3730-7TG37-4B_0
6SL3730-7TG41-0B_0
6SL3730-7TG41-3B_0
Technical specifications
"Fuse switch disconnector" checkback contacts
Max. load current: 3 A
Max. switching voltage: 250 V AC
Input current
Overload trip
Line Module
(L)
840 A
1.0
985 A
0.9
1405 A
1.0
2 x 936 A
1.0
2 x 1335 A
0.9
1025 A
0.9
1270 A
0.9
2 x 698 A
0.7
2 x 974 A
1.0
2 x 1206 A
1.0
Cabinet Modules
5.1 Line Connection Modules
Short-time
Short-circuit
delayed short-
release delay
circuit release
(tsd)
(S)
2
0
2
0
2
0
2
0
2
0
2
0
2
0
2
0
2
0
2
0