L55, Cabinet Anti-Condensation Heating - Siemens SINAMICS S120 Equipment Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Options

8.26 L55, cabinet anti-condensation heating

8.26
L55, cabinet anti-condensation heating
Availability of option
This option is available for the following S120 Cabinet Modules:
● Line Connection Module
● Basic Line Module
● Smart Line Module
● Active Line Module
● Motor Module in chassis format
● Booksize Base Cabinet
● Auxiliary Power Supply Module
Description
The cabinet anti-condensation heating can be used at low ambient temperatures and high
levels of humidity to prevent the formation of condensation.
A 100 W heater (-E240) is used for a 400 mm and 600 mm cabinet. Two 100 W heaters
(-E240, -E241) are used for cabinet widths of 800 mm or greater.
The power supply (110 to 230 V AC) must be provided externally and protected with a fuse
of up to 10 A.
-X240 – Connection for cabinet anti-condensation heating
Table 8- 31
Terminal
1
2
3
max. connectable cross section: 4 mm²
Since the voltage is supplied from an external source, voltage may still be present in the
cabinets even when the main breakers in all units are open.
You must observe the "five safety rules" during servicing.
402
Terminal block -X240 – Connection for cabinet anti-condensation heating
Designation
L1
N
PE
DANGER
Technical specifications
110 to 230 V AC voltage supply
Current demand:
- min.: approx. 0.43 A (for 230 V AC, 100 W)
- max.: approx. 1.8 A (for 110 V AC, 200 W)
Protective conductor
S120 Cabinet Modules Equipment Manual
Manual, (GH5), 10/2008, A5E00427098A