If the terminals are not reconnected to the actual line voltage:
• The required cooling capacity cannot be provided because the fan rotates too slowly;
• The fan fuses may blow due to an overcurrent.
Note
With the fan transformer (500 to 690 V 2 AC), a jumper is inserted between terminal "600 V"
and terminal "CON" ((1) in the picture above). Terminal "CON" is for internal use.
The order numbers for fan fuses that have blown can be found in the spare parts list.
Table 4- 9
Table 4- 10
S120 Cabinet Modules Equipment Manual
Manual, (GH5), 10/2008, A5E00427098A
CAUTION
Line voltage assignments for setting the fan transformer (380 to 480 V 2 AC)
Line voltage
380 V ± 10%
400 V ± 10%
440 V ± 10%
480 V ± 10%
Line voltage assignments for setting the fan transformer (500 to 690 V 2 AC)
Line voltage
500 V ± 10%
525 V ± 10%
575 V ± 10%
600 V ± 10%
660 V ± 10%
690 V ± 10%
Fan transformer tap (-T1/-T2 –T10, -T20)
380 V
400 V
440 V
480 V
Fan transformer tap (-T1/-T2 -T10, -T20)
500 V
525 V
575 V
600 V
660 V
690 V
Electrical installation
4.5 Connections
73