Troubleshooting for FFQ Series
5.3

Fan Motor or Related Abnormality

A6
Error Code
Method of Error
The signal from the fan motor detects abnormal fan speed.
Detection
Error Decision
The fan rotations are not detected while the output voltage to the fan is at its maximum.
Conditions
 Disconnection, short circuit or disengagement of connector in fan motor harness
Supposed
 Defective fan motor (disconnection, poor insulation)
Causes
 Abnormal signal from fan motor (faulty circuit)
 Defective indoor unit PCB
 Momentary fluctuation of power supply voltage
 Fan motor lock
 Fan does not rotate due to tangled foreign matters.
Troubleshooting
Note:
1. Check the connector of fan motor. (Power supply cable)
2. Turn OFF the power supply.
3. Measure the resistance between the terminals at the motor side connectors to check that there
FFQ series
169
(Caused by motor or other external factors)
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn off the power supply.
Is there any
foreign matter around
the fan?
NO
Is the
harness from the
fan motor correctly
connected to the
indoor unit
PCB?
YES
Check the fan motor
connector. (See the Note.)
Is there
short circuit between
the terminals?
YES
is no short circuit, while the connector is disconnected.
(1) Red
(2) White
(3) Black
(R18060)
YES
NO
NO
Measuring points
(1) - (3)
(2) - (3)
SiUS181305E
Remove the foreign matter.
Connect the connector
correctly.
X20A: FFQ series
Replace the fan motor.
Replace the indoor unit PCB.
(R18389)
Resistance for judgement
88.2  ± 10%
85.5  ± 10%
Troubleshooting