Daikin CTXG09QVJUW Service Manual

Daikin CTXG09QVJUW Service Manual

Multi-split type air conditioners 2/3mxl-q series
Hide thumbs Also See for CTXG09QVJUW:
Table of Contents

Advertisement

SiUS121632EA
Service
Manual
Multi-Split Type Air Conditioners
2/3MXL-Q Series
[Applied Models]
Inverter Multi : Heat Pump

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CTXG09QVJUW and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Daikin CTXG09QVJUW

  • Page 1 SiUS121632EA Service Manual Multi-Split Type Air Conditioners 2/3MXL-Q Series [Applied Models] Inverter Multi : Heat Pump...
  • Page 2 SiUS121632EA Multi-Split Type Air Conditioners 2/3MXL-Q Series Heat Pump Indoor Unit CTXG09QVJUW FDXS09LVJU FVXS09NVJU FFQ09Q2VJU CTXG09QVJUS FDXS12LVJU FVXS12NVJU FFQ12Q2VJU CTXG12QVJUW CDXS15LVJU FVXS15NVJU FFQ15Q2VJU CTXG12QVJUS CDXS18LVJU FVXS18NVJU FFQ18Q2VJU CTXG18QVJUW CTXG18QVJUS CTXS07LVJU FTXS09LVJU FTXS12LVJU FTXS15LVJU FTXS18LVJU Outdoor Unit 2MXL18QMVJU 3MXL24QMVJU Table of Contents...
  • Page 3: Table Of Contents

    SiUS121632EA 1. Safety Cautions..................vi 1.1 Warnings and Cautions Regarding Safety of Workers.........vi 1.2 Warnings and Cautions Regarding Safety of Users........viii 2. Icons Used ....................xi Part 1 List of Functions ..............1 1. Functions..................... 2 Part 2 Specifications ............... 8 1.
  • Page 4 SiUS121632EA 2.10 POWERFUL Operation ................53 2.11 Multi-Monitor Lamp/TIMER Lamp .............. 54 2.12 Clock Setting ....................55 2.13 WEEKLY TIMER Operation ............... 56 2.14 Other Functions..................62 3. FFQ Series Functions ................64 3.1 Airflow Direction Control................64 3.2 Fan Speed Control for Indoor Unit ............. 64 3.3 Program Dry Operation ................
  • Page 5 SiUS121632EA 2. Troubleshooting with LED ...............118 2.1 Indoor Unit....................118 2.2 Outdoor Unit ..................... 120 3. Service Diagnosis ................... 121 3.1 CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series ........121 3.2 FFQ Series ....................127 4. Code Indication on Remote Controller ............ 133 4.1 CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series ........
  • Page 6 SiUS121632EA 7.14 Compressor Sensor System Abnormality ..........178 7.15 Position Sensor Abnormality ..............180 7.16 CT or Related Abnormality ............... 182 7.17 Thermistor or Related Abnormality (Outdoor Unit)........184 7.18 Electrical Box Temperature Rise.............. 186 7.19 Radiation Fin Temperature Rise .............. 187 7.20 Output Overcurrent Detection ..............
  • Page 7: Safety Cautions

    SiUS121632EA Safety Cautions 1. Safety Cautions Be sure to read the following safety cautions before conducting repair work. After the repair work is complete, be sure to conduct a test operation to ensure that the equipment operates normally, and explain the cautions for operating the product to the customer. Caution Items The caution items are classified into Warning and...
  • Page 8 Safety Cautions SiUS121632EA Warning Do not turn the air conditioner on or off by plugging in or unplugging the power cable. Plugging in or unplugging the power cable to operate the equipment may cause an electrical shock or fire. Be sure to wear a safety helmet, gloves, and a safety belt when working in a high place (more than 2 m (6.5 ft)).
  • Page 9: Warnings And Cautions Regarding Safety Of Users

    SiUS121632EA Safety Cautions Caution Conduct welding work in a well-ventilated place. Using a welder in an enclosed room may cause oxygen deficiency. Warnings and Cautions Regarding Safety of Users Warning Do not store the equipment in a room with fire sources (e.g., naked flames, gas appliances, electric heaters).
  • Page 10 Safety Cautions SiUS121632EA Warning Do not mix air or gas other than the specified refrigerant (R-32 / R-410A / R- 22) in the refrigerant system. If air enters the refrigerant system, an excessively high pressure results, causing equipment damage and injury. If the refrigerant gas leaks, be sure to locate the leaking point and repair it before charging the refrigerant.
  • Page 11 SiUS121632EA Safety Cautions Caution Check the earth / grounding, and repair it if the equipment is not properly earthed / grounded. Improper earth / grounding may cause an electrical shock. Be sure to measure insulation resistance after the repair, and make sure that the resistance is 1 MΩ...
  • Page 12: Icons Used

    Icons Used SiUS121632EA 2. Icons Used The following icons are used to attract the attention of the reader to specific information. Icon Type of Description Information Warning A Warning is used when there is danger of personal injury. Warning Caution A Caution is used when there is danger that the reader, through incorrect manipulation, may damage equipment, lose data, get an Caution...
  • Page 13: Part 1 List Of Functions

    SiUS121632EA Part 1 List of Functions 1. Functions..................... 2 List of Functions...
  • Page 14: Functions

    Functions SiUS121632EA 1. Functions Category Functions Category Functions Basic Inverter (with inverter power control) Health & Air-purifying filter — Functions Cleanliness Operation limit for cooling — Titanium apatite deodorizing filter (option) Operation limit for heating — Longlife filter (option) — PAM control —...
  • Page 15 SiUS121632EA Functions Category Functions Category Functions Basic Inverter (with inverter power control) Health & Air-purifying filter — — Functions Cleanliness Operation limit for cooling — — Titanium apatite deodorizing filter Operation limit for heating — — Longlife filter (option) — —...
  • Page 16 Functions SiUS121632EA Category Functions Category Functions Basic Inverter (with inverter power control) Health & Air-purifying filter — — Functions Cleanliness Operation limit for cooling — — Titanium apatite deodorizing filter — — Operation limit for heating — — Longlife filter (option) —...
  • Page 17 SiUS121632EA Functions Category Functions Category Functions Basic Inverter (with inverter power control) Health & Air-purifying filter — Functions Cleanliness Operation limit for cooling — Titanium apatite deodorizing filter Operation limit for heating — Longlife filter (option) — PAM control — Air filter (prefilter) Compressor Oval scroll compressor...
  • Page 18 Functions SiUS121632EA Category Functions Category Functions Basic Inverter (with inverter power control) Health & Auto cleaning filter — — Functions Cleanliness Operation limit for cooling — — Air-purifying filter — — Operation limit for heating — — Titanium apatite deodorizing filter —...
  • Page 19 SiUS121632EA Functions Category Functions Category Functions Basic Inverter (with inverter power control) Health & Air-purifying filter — — Functions Cleanliness Operation limit for cooling Titanium apatite deodorizing filter — — Refer to P. 240 Operation limit for heating Longlife filter (option) —...
  • Page 20: Part 2 Specifications

    SiUS121632EA Part 2 Specifications 1. Indoor Unit....................9 1.1 CTXG Series ....................9 1.2 CTXS, FTXS Series ................... 11 1.3 FDXS, CDXS Series................... 13 1.4 FVXS Series....................14 1.5 FFQ Series ....................15 2. Outdoor Unit....................16 Specifications...
  • Page 21: Indoor Unit

    SiUS121632EA Indoor Unit 1. Indoor Unit CTXG Series 60 Hz, 208 - 230 V CTXG09QVJUW CTXG09QVJUS Model Cooling Heating Cooling Heating Rated Capacity 9 kBtu/h Class 9 kBtu/h Class Front Panel Color White Silver 279 (7.9) 367 (10.4) 279 (7.9) 367 (10.4)
  • Page 22 Indoor Unit SiUS121632EA 60 Hz, 208 - 230 V CTXG18QVJUW CTXG18QVJUS Model Cooling Heating Cooling Heating Rated Capacity 18 kBtu/h Class 18 kBtu/h Class Front Panel Color White Silver 364 (10.3) 438 (12.4) 364 (10.3) 438 (12.4) 286 (8.1) 350 (9.9) 286 (8.1) 350 (9.9) Airflow Rate...
  • Page 23: Ctxs, Ftxs Series

    SiUS121632EA Indoor Unit CTXS, FTXS Series 60 Hz, 208 - 230 V CTXS07LVJU Model Cooling Heating Rated Capacity 7 kBtu/h Class Front Panel Color White 332 (9.4) 350 (9.9) 261 (7.4) 290 (8.2) Airflow Rate (m³/min) 194 (5.5) 233 (6.6) 145 (4.1) 219 (6.2) Type...
  • Page 24 Indoor Unit SiUS121632EA 60 Hz, 208 - 230 V FTXS15LVJU FTXS18LVJU Model Cooling Heating Cooling Heating Rated Capacity 15 kBtu/h Class 18 kBtu/h Class Front Panel Color White White 568 (16.1) 593 (16.8) 583 (16.5) 625 (17.7) 477 (13.5) 505 (14.3) 484 (13.7) 526 (14.9) Airflow Rate...
  • Page 25: Fdxs, Cdxs Series

    SiUS121632EA Indoor Unit FDXS, CDXS Series 60 Hz, 208 - 230 V FDXS09LVJU FDXS12LVJU Model Cooling Heating Cooling Heating Rated Capacity 9 kBtu/h Class 12 kBtu/h Class External Static Pressure inAq (Pa) 0.12 (30) 0.12 (30) 305 (8.6) 305 (8.6) 305 (8.6) 305 (8.6) 280 (7.9)
  • Page 26: Fvxs Series

    Indoor Unit SiUS121632EA FVXS Series 60 Hz, 208 - 230 V FVXS09NVJU FVXS12NVJU Model Cooling Heating Cooling Heating Rated Capacity 9 kBtu/h Class 12 kBtu/h Class Front Panel Color White White 290 (8.2) 311 (8.8) 300 (8.5) 332 (9.4) 230 (6.5) 244 (6.9) 237 (6.7) 258 (7.3)
  • Page 27: Ffq Series

    SiUS121632EA Indoor Unit FFQ Series 60 Hz, 208 - 230 V FFQ09Q2VJU FFQ12Q2VJU Model Cooling Heating Cooling Heating Rated Capacity 9 kBtu/h Class 12 kBtu/h Class Model BYFQ60B3W1 BYFQ60B3W1 Color White White Decoration Panel Dimensions in. (mm) 2-3/16 × 27-9/16 × 27-9/16 (55 × 700 × 700) 2-3/16 ×...
  • Page 28: Outdoor Unit

    Outdoor Unit SiUS121632EA 2. Outdoor Unit 60 Hz, 208 - 230 V 2MXL18QMVJU Model Cooling Heating — 4.20 Btu/W·h 12.7 — SEER / HSPF 17.0 10.3 Casing Color Ivory White Type Hermetically Sealed Swing Type Compressor Model 2YC63AAXD Motor Output 1,920 Model FVC50K...
  • Page 29 SiUS121632EA Outdoor Unit 60 Hz, 208 - 230 V 3MXL24QMVJU Model Cooling Heating — 4.56 Btu/W·h 12.7 — SEER / HSPF 17.9 12.5 Casing Color Ivory White Type Hermetically Sealed Swing Type Compressor Model 2YC63AAXD Motor Output 1,920 Model FVC50K Refrigerant Oil Charge oz (L)
  • Page 30: Part 3 Printed Circuit Board Connector Wiring Diagram

    SiUS121632EA Part 3 Printed Circuit Board Connector Wiring Diagram 1. Indoor Unit....................19 1.1 CTXG09/12/18QVJUW(S)................19 1.2 CTXS07LVJU, FTXS09/12LVJU ..............21 1.3 FTXS15/18LVJU ..................23 1.4 FDXS09/12LVJU, CDXS15/18LVJU ............25 1.5 FVXS09/12/15/18NVJU................27 1.6 FFQ09/12/15/18Q2VJU................29 2. Wired Remote Controller................30 2.1 BRC1E73 ....................30 3.
  • Page 31: Indoor Unit

    SiUS121632EA Indoor Unit 1. Indoor Unit CTXG09/12/18QVJUW(S) Control PCB (A1P) 1) S21 Connector for centralized control (HA) 2) S25 Connector for INTELLIGENT EYE sensor PCB (A3P) 3) S32 Indoor heat exchanger thermistor 4) S41 Connector for swing motors 5) S42 Connector for reduction motor (front panel mechanism) and limit switch 6) S46 Connector for display/signal receiver PCB (A2P)
  • Page 32 Indoor Unit SiUS121632EA Display/Signal Receiver PCB 1) S51 Connector for control PCB (A1P) (A2P) 2) S52 Connector for room temperature thermistor 3) S1W Indoor unit ON/OFF button 4) H1P LED for operation (multi-color) 5) H2P LED for INTELLIGENT EYE (green) 6) JA Address setting jumper ∗...
  • Page 33: Ctxs07Lvju, Ftxs09/12Lvju

    SiUS121632EA Indoor Unit CTXS07LVJU, FTXS09/12LVJU Control PCB (PCB1) 1) S1 Connector for DC fan motor 2) S21 Connector for centralized control (HA) 3) S25 Connector for INTELLIGENT EYE sensor PCB (PCB4) 4) S32 Indoor heat exchanger thermistor 5) S41 Connector for swing motors 6) S46 Connector for display PCB (PCB3) 7) S47...
  • Page 34 Indoor Unit SiUS121632EA Signal Receiver PCB (PCB2) 1) S48 Connector for control PCB (PCB1) 3P210728-1 Display PCB (PCB3) 1) S49 Connector for control PCB (PCB1) 2) SW1 Indoor unit ON/OFF button 3) LED1 (H1P) LED for operation (green) 4) LED2 (H2P) LED for timer (yellow) 5) LED3 (H3P) LED for INTELLIGENT EYE (green)
  • Page 35: Ftxs15/18Lvju

    SiUS121632EA Indoor Unit FTXS15/18LVJU Control PCB (PCB1) 1) S1 Connector for DC fan motor 2) S21 Connector for centralized control (HA) 3) S25 Connector for INTELLIGENT EYE sensor PCB (PCB4) 4) S32 Indoor heat exchanger thermistor 5) S41 Connector for swing motors 6) S46 Connector for display PCB (PCB3) 7) S47...
  • Page 36 Indoor Unit SiUS121632EA Signal Receiver PCB (PCB2) 1) S48 Connector for control PCB (PCB1) 3P224121-1 Display PCB (PCB3) 1) S49 Connector for control PCB (PCB1) 2) SW1 Indoor unit ON/OFF button 3) LED1 (H1P) LED for operation (green) 4) LED2 (H2P) LED for timer (yellow) 5) LED3 (H3P) LED for INTELLIGENT EYE (green)
  • Page 37: Fdxs09/12Lvju, Cdxs15/18Lvju

    SiUS121632EA Indoor Unit FDXS09/12LVJU, CDXS15/18LVJU Control PCB (A1P) 1) S1 Connector for AC fan motor 2) S7 Connector for AC fan motor (Hall IC) 3) S21 Connector for centralized control (HA) 4) S26 Connector for display/signal receiver PCB (A2P) 5) S32 Connector for indoor heat exchanger thermistor 6) H1, H2, H3 Connector for terminal block...
  • Page 38 Indoor Unit SiUS121632EA Display/Signal Receiver PCB 1) S1 Connector for control PCB (A1P) (A2P) 2) SW1 (S1W) Indoor unit ON/OFF button 3) LED2 (H2P) LED for timer (yellow) 4) LED3 (H3P) LED for operation (green) 5) RTH1 (R1T) Room temperature thermistor LED3 LED2 RTH1...
  • Page 39: Fvxs09/12/15/18Nvju

    SiUS121632EA Indoor Unit FVXS09/12/15/18NVJU Control PCB (PCB2) 1) S1 Connector for DC fan motor 2) S21 Connector for centralized control (HA) 3) S26 Connector for service PCB (PCB3) 4) S32 Indoor heat exchanger thermistor 5) S41 Connector for lower air outlet motor 6) S42 Connector for swing motor 7) S46...
  • Page 40 Indoor Unit SiUS121632EA Sensor PCB (PCB1) 1) S49 Connector for control PCB (PCB2) 2) RTH2 (R1T) Room temperature thermistor RTH2 3P191450-1 Service PCB (PCB3) 1) S27 Connector for control PCB (PCB2) 2) SW2 (S2W)-4 Switch for upward airflow limit setting ∗...
  • Page 41: Ffq09/12/15/18Q2Vju

    SiUS121632EA Indoor Unit FFQ09/12/15/18Q2VJU Control PCB (A1P) 1) X15A Connector for float switch 2) X16A Connector for room temperature thermistor (suction air thermistor) 3) X17A, X18A Connector for indoor heat exchanger thermistor 4) X20A Connector for DC fan motor 5) X24A Connector for transmitter board (when the wireless remote controller (option) is used) 6) X25A...
  • Page 42: Wired Remote Controller

    Wired Remote Controller SiUS121632EA 2. Wired Remote Controller BRC1E73 Wired Remote Controller PCB 1) P1, P2 Terminal for indoor unit 2) R4T Room temperature thermistor 2P298037-7 Printed Circuit Board Connector Wiring Diagram...
  • Page 43: Wireless Remote Controller Kit

    SiUS121632EA Wireless Remote Controller Kit 3. Wireless Remote Controller Kit BRC082A41W, BRC082A42W(S) Transmitter Board (A2P) 1) X1A Connector for receiver (A3P) 2) X2A Connector for control PCB (A1P) 3) SS1 MAIN/SUB setting switch ∗ Refer to page 223 for details. 4) SS2 Address setting switch ∗...
  • Page 44: Outdoor Unit

    Outdoor Unit SiUS121632EA 4. Outdoor Unit Main PCB (PCB1) 1) S Connector for terminal board (indoor - outdoor transmission) 2) S15 Connector for COOL/HEAT mode lock ∗ Refer to page 212 for details. 3) S20 (white) Connector for electronic expansion valve coil A port 4) S21 (red) Connector for electronic expansion valve coil B port 5) S22 (blue)
  • Page 45 SiUS121632EA Outdoor Unit E1, E2 HL1, HN1 V401 S201 U, V, W S202 2P350358-12 Printed Circuit Board Connector Wiring Diagram...
  • Page 46 Outdoor Unit SiUS121632EA Service Monitor PCB (PCB2) 1) S501, S502 Connector for main PCB (PCB1) 2) LED A LED for service monitor (green) 3) LED1 - LED5 LED for service monitor (red) 4) SW1 Forced operation ON/OFF switch ∗ Refer to page 203 for details. 5) SW2 Operation mode switch ∗...
  • Page 47: Part 4 Functions And Control

    SiUS121632EA Part 4 Functions and Control 1. Common Functions ...................37 1.1 Temperature Control .................. 37 1.2 Frequency Principle..................37 2. CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions....40 2.1 Airflow Direction Control................40 2.2 Fan Speed Control for Indoor Unit ............. 44 2.3 Program Dry Operation ................
  • Page 48 SiUS121632EA 4.10 Liquid Compression Protection Function............ 88 4.11 Defrost Control ................... 89 4.12 Low Hz High Pressure Limit ............... 90 4.13 Electronic Expansion Valve Control ............91 4.14 Malfunctions ....................96 Functions and Control...
  • Page 49: Common Functions

    SiUS121632EA Common Functions 1. Common Functions Temperature Control Definitions of The definitions of temperatures are classified as following. Temperatures Room temperature: temperature of lower part of the room Set temperature: temperature set by remote controller Room thermistor temperature: temperature detected by room temperature thermistor Target temperature: temperature determined by microcomputer Target temperature Room thermistor temperature...
  • Page 50 Common Functions SiUS121632EA Inverter Principle To regulate the capacity, a frequency control is needed. The inverter makes it possible to control the rotation speed of the compressor. The following table explains the inverter principle: Phase Description The supplied AC power source is converted into the DC power source for the present. The DC power source is reconverted into the three phase AC power source with variable frequency.
  • Page 51 SiUS121632EA Common Functions Frequency Limits The following functions regulate the minimum and maximum frequency: Frequency Functions Four way valve operation compensation. Refer to page 84. High Compressor protection function. Refer to page 85. Discharge pipe temperature control. Refer to page 85. Input current control.
  • Page 52: Ctxg, Ctxs, Ftxs, Cdxs, Fdxs, Fvxs Series Functions

    CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions SiUS121632EA 2. CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions Airflow Direction Control Applicable CTXG09/12/18QVJUW(S) CTXS07LVJU Models FTXS09/12/15/18/24LVJU FVXS09/12/15/18NVJU Power-Airflow The large flap sends a large volume of air downward to the floor and provides an optimum control in cooling, dry and heating operation.
  • Page 53 SiUS121632EA CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions CTXS, FTXS Series Flap (up and down) Louver (right and left) Cooling/Dry Heating 5˚ 07/09/12 class 15˚ 30˚ 35˚ 30˚ 30˚ 55˚ 65˚ 45˚ 65˚ 70˚ 80˚ (R11404) (R13527) (R11402) (R11403) 15˚...
  • Page 54 CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions SiUS121632EA 3-D Airflow CTXG, CTXS, FTXS Series Alternative repetition of vertical and horizontal swing motions enables uniform air-conditioning of the entire room. When the horizontal swing and vertical swing are both set to automatic operation, the airflow becomes 3-D airflow.
  • Page 55 SiUS121632EA CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions Airflow Selection FVXS Series Setting Airflow direction can be set with the airflow selection switch. Open the front panel. Air is blown from the upper outlet only. The blow pattern is automatically decided depending on mode and conditions.
  • Page 56: Fan Speed Control For Indoor Unit

    CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions SiUS121632EA Fan Speed Control for Indoor Unit Outline Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H, and HH. The airflow rate can be automatically controlled depending on the difference between the room thermistor temperature and the target temperature.
  • Page 57: Program Dry Operation

    SiUS121632EA CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions Program Dry Operation Outline Program dry operation removes humidity while preventing the room temperature from lowering. Since the microcomputer controls both the temperature and airflow rate, the temperature adjustment and FAN setting buttons are inoperable. Details The microcomputer automatically sets the temperature and airflow rate.
  • Page 58: Automatic Operation

    CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions SiUS121632EA Automatic Operation Outline Automatic Cooling/Heating Function When the automatic operation is selected with the remote controller, the microcomputer automatically determines the operation mode as cooling or heating according to the room temperature and the set temperature at start-up.
  • Page 59: Thermostat Control

    SiUS121632EA CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions CDXS, FDXS, FVXS series Cooling Operation Target temperature + 2.5˚C (+4.5˚F) Target temperature – 2.0˚C (–3.6˚F) Target temperature + 1.5˚C (+2.7˚F) = Thermostat OFF = Thermostat OFF Target temperature – 3.0˚C (–5.4˚F) Heating Operation (R22000) Ex: When the target temperature is 25°C (77°F)
  • Page 60: Night Set Mode

    CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions SiUS121632EA CTXS, FTXS series Room thermistor temperature – target temperature Zone A 2.0˚C (3.6˚F) 2.0˚C (3.6˚F) Zone B 1.5˚C (2.7˚F) Zone C 1.0˚C (1.8˚F) 0.5˚C (0.9˚F) (R24033) CDXS, FDXS, FVXS series Room thermistor temperature – target temperature Zone A 1.5˚C (2.7˚F) Zone B...
  • Page 61: Econo Operation

    SiUS121632EA CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions ECONO Operation Applicable CTXG09/12/18QVJUW(S) CTXS07LVJU Models FDXS09/12LVJU CDXS15/18LVJU FTXS09/12/15/18/24LVJU FVXS09/12/15/18NVJU Outline ECONO operation reduces the maximum operating current and the power consumption. This operation is particularly convenient for energy-saving. It is also a major bonus when breaker capacity does not allow the use of multiple electrical devices and air conditioners.
  • Page 62: 2-Area Intelligent Eye Operation

    CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions SiUS121632EA 2-Area INTELLIGENT EYE Operation Applicable CTXG09/12/18QVJUW(S) Models Outline The following functions can be performed by the microcomputer with a motion sensor. 1. Reduction of the capacity when there is nobody in the room in order to save electricity (energy saving operation) 2.
  • Page 63 SiUS121632EA CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions 2. Motions (in cooling) within within 20 min. 20 min. within 20 min. 20 min. Human detection signal ↑ ↑ ↑ Reset Reset Reset 1 ~ 2˚C (1.8 ~ 3.6 ˚F) Target temperature Remote controller Sensor button...
  • Page 64: Intelligent Eye Operation

    CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions SiUS121632EA INTELLIGENT EYE Operation Applicable CTXS07LVJU FTXS09/12/15/18/24LVJU Models Outline The microcomputer detects the presence of humans in the room with a motion sensor and reduces the capacity when there is nobody in the room in order to save electricity. Details 1.
  • Page 65: Powerful Operation

    SiUS121632EA CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions 2.10 POWERFUL Operation Outline In order to exploit the cooling and heating capacity to full extent, the air conditioner can be operated by increasing the indoor fan rotating speed and the compressor frequency. Details When POWERFUL button is pressed, the fan speed and target temperature are converted to the following states for 20 minutes.
  • Page 66: Multi-Monitor Lamp/Timer Lamp

    CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions SiUS121632EA 2.11 Multi-Monitor Lamp/TIMER Lamp Applicable CTXG09/12/18QVJUW(S) Models Features Current operation mode is displayed in color of the lamp of the indoor unit. Operating status can be monitored even in automatic operation in accordance with the actual operation mode. Multi-monitor lamp/ TIMER lamp (R19925)
  • Page 67: Clock Setting

    SiUS121632EA CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions 2.12 Clock Setting ARC452 Series The clock can be set by taking the following steps: 1. Press CLOCK button. ARC466 Series → is displayed. MON and blink. 2. Press SELECT or SELECT button to set the clock to the current day of the week.
  • Page 68: Weekly Timer Operation

    CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions SiUS121632EA 2.13 WEEKLY TIMER Operation Applicable CTXG09/12/18QVJUW(S) CTXS07LVJU Models FTXS09/12/15/18/24LVJU FVXS09/12/15/18NVJU Outline Up to 4 timer settings can be saved for each day of the week (up to 28 settings in total). The 3 items: ON/OFF, temperature, and time can be set.
  • Page 69 SiUS121632EA CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions To use WEEKLY TIMER operation Setting mode • Make sure the day of the week and time are set. If not, set the day of the week and time. program 1 program 2 program 3 program 4...
  • Page 70 CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions SiUS121632EA Press to select the desired time. • The time can be set between 0:00 and 23:50 in 10-minute intervals. • To return to the ON/OFF TIMER mode setting, press • Proceed to STEP when setting the OFF TIMER.
  • Page 71 SiUS121632EA CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions Copy mode • A reservation made once can be copied to another day of the week. The whole reservation of the selected day of the week will be copied. program 1 program 2 program 3 program 4 [Monday]...
  • Page 72 CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions SiUS121632EA Confirming a reservation • The reservation can be confirmed. Setting Displays Normal Confirmation Press • The day of the week and the reservation number of the current day will be displayed. Press to select the day of the week and the reservation number to be confirmed.
  • Page 73 SiUS121632EA CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions To delete reservations An individual reservation Press • The day of the week and the reservation number will be displayed. Press to select the day of the week and the reservation number to be deleted. Press •...
  • Page 74: Other Functions

    CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions SiUS121632EA 2.14 Other Functions 2.14.1 Hot-Start Function In order to prevent the cold air blast that normally occurs when heating operation starts, the temperature of the indoor heat exchanger is detected, and the airflow is either stopped or significantly weakened resulting in comfortable heating.
  • Page 75 SiUS121632EA CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions FVXS Series ON/OFF button (R23926) 2.14.4 Auto-restart Function If a power failure (even a momentary one) occurs during the operation, the system restarts automatically in the same conditions as before when the power supply is restored to the conditions prior to the power failure.
  • Page 76: Ffq Series Functions

    FFQ Series Functions SiUS121632EA 3. FFQ Series Functions Airflow Direction Control Outline There are two types of airflow direction settings. Automatic swing setting The flaps automatically oscillate up and down. Indoor unit (Automatic swing) (Automatic swing) (R24069) Airflow direction fixed setting You can select from one of the fixed directions.
  • Page 77: Program Dry Operation

    SiUS121632EA FFQ Series Functions Program Dry Operation Outline Program dry operation removes humidity while preventing the room temperature from lowering. Since the microcomputer controls both the temperature and airflow rate, the temperature adjustment and FAN setting buttons are inoperable. Details The microcomputer automatically sets the temperature and airflow rate.
  • Page 78: Clock And Calendar Setting (With Wired Remote Controller Brc1E73)

    FFQ Series Functions SiUS121632EA Clock and Calendar Setting (With Wired Remote Controller BRC1E73) Press Menu/OK button to display the main menu screen. Press buttons to select Clock & Calendar on the main menu screen. Press Menu/OK button to display the clock &...
  • Page 79 SiUS121632EA FFQ Series Functions Select Hour with buttons. Change the hour with buttons. Holding down the button causes the number to change continuously. Select Minute with buttons. Change the minute with buttons. Holding down the button causes the number to change continuously. Press Menu/OK button.
  • Page 80: Schedule Timer Operation (With Wired Remote Controller Brc1E73)

    FFQ Series Functions SiUS121632EA Schedule TIMER Operation (With Wired Remote Controller BRC1E73) Outline Day settings are selected from 4 patterns: 7Days Weekday/Sat/Sun Weekday/Weekend Everyday Up to 5 actions can be set for each day. Details Set the startup time and operation stop time. Startup time, cooling and heating temperature setpoints can be configured.
  • Page 81 SiUS121632EA FFQ Series Functions Daily Patterns The schedule screen will appear. Press buttons to select Daily Patterns on the schedule screen. The daily patterns screen will appear when Menu/OK button is pressed. Press buttons to select 7 Days Weekday/Sat/Sun Weekday/Weekend Everyday the daily patterns screen.
  • Page 82 FFQ Series Functions SiUS121632EA Press buttons to move the highlighted item and press buttons to configure ON/OFF/-- settings. --, ON, or OFF changes in sequence when buttons are pressed. ON: The temperature setpoints can be configured. OFF: The setback temperature setpoints can be configured.
  • Page 83 SiUS121632EA FFQ Series Functions Enabling or disabling the schedule Display the schedule screen. Press buttons to select Enable / Disable on the schedule screen. Press Menu/OK button to display the enable/disable screen. Press buttons to select Enable Disable on the enable/disable screen.
  • Page 84: Setback Function (With Wired Remote Controller Brc1E73)

    FFQ Series Functions SiUS121632EA Setback Function (With Wired Remote Controller BRC1E73) The Setback function can be used to maintain the space temperature in an assigned range for an unoccupied period. The setback icon flashes on the LCD of wired remote controller when the unit is turned on by the setback control.
  • Page 85 SiUS121632EA FFQ Series Functions 3.7.2 If the Float Switch is OFF with the Thermostat ON in Cooling Operation ∗2 ∗1 ∗4 ∗3 Float switch 5 sec. 5 sec. Thermostat (running) Error display Drain pump 5 min. 5 sec. 5 min. 5 sec.
  • Page 86: Hot Start Control (In Heating Operation Only)

    FFQ Series Functions SiUS121632EA 3.7.4 If the Float Switch Turns OFF and ON Continuously, or the Float Switch Turns OFF While AF Displayed ∗1 ∗2 ∗3 Float Switch 5 sec. 5 sec. 5 sec. 5 sec. 5 sec. Thermostat (running) Error Display Drain Pump 5 min.
  • Page 87: Presence And Floor Sensors (Option)

    SiUS121632EA FFQ Series Functions Presence and Floor Sensors (Option) Outline With the human presence signal and the floor temperature signal from the optional sensor kit, the system provides the energy saving control, or the comfortable temperature control and airflow direction control preventing the direct draft to the human. To use sensor related functions, a wired remote controller (BRC1E73) and optional sensor kit (BRYQ60A2W(S)) are necessary to be installed.
  • Page 88 FFQ Series Functions SiUS121632EA 2. Auto-setback by sensor (with presence sensor) After pre-determined time has elapsed without detection of human presence, the unit automatically shifts the target temperature gradually for energy saving. The target temperature displayed on the remote controller remains same as the initial set value during the above change of target temperature.
  • Page 89 SiUS121632EA FFQ Series Functions 3. Auto-off by sensor (with presence sensor) After pre-determined time has elapsed without detection of human presence, the unit automatically stops operation. The auto-off time can be set between 1- 24 hours by the hour. Once the unit stops operation by auto-off function, the system would not restart even if the human is detected again.
  • Page 90: Other Functions

    FFQ Series Functions SiUS121632EA 3.10 Other Functions 3.10.1 Signal Receiving Sign When the indoor unit receives a signal from the remote controller, the unit emits a signal receiving sound. 3.10.2 Auto-restart Function If a power failure (even a momentary one) occurs during the operation, the system restarts automatically in the same conditions as before when the power supply is restored to the conditions prior to the power failure.
  • Page 91: Control Specification

    SiUS121632EA Control Specification 4. Control Specification Thermistor Functions (3) Outdoor Expansion valve (5) Liquid Pipe Temperature Thermistor Thermistor (2) Outdoor Heat Exchanger Thermistor Four way valve (1) Discharge Pipe Thermistor (7) Room (6) Indoor Heat Compressor (4) Gas Pipe Temperature Exchanger Thermistor Thermistor...
  • Page 92 Control Specification SiUS121632EA (5) Liquid Pipe Liquid pipe thermistor is used to protect the compressor against liquid attack during cooling Thermistor operation. In case of low outdoor temperature operation, the system compares the indoor heat exchanger temperature with the liquid pipe temperature to detect disturbances in the refrigerant flow. If any, the system adjusts the opening of the electronic expansion valve to control the refrigerant flow.
  • Page 93: Mode Hierarchy

    SiUS121632EA Control Specification Mode Hierarchy Outline Air conditioner control has normal operation mode, forced operation mode, and power transistor test mode for installation and servicing. Details Air conditioner control mode Forced operation mode Forced cooling operation (for pump down operation) Forced heating operation Wiring error check operation Power transistor test mode...
  • Page 94: Frequency Control

    Control Specification SiUS121632EA Frequency Control Outline Frequency that corresponds to each room’s capacity is determined according to the difference between the target temperature and the temperature of each room. When the shift of the frequency is less than zero (∆F<0) by PI control, the target frequency is used as the command frequency.
  • Page 95 SiUS121632EA Control Specification Parameters Q value Indoor unit output determined from indoor unit volume, airflow rate and other factors. S value: Indoor Unit Capacity An S value is the capacity of the indoor unit, and is used for frequency command. Capacity S value Capacity...
  • Page 96: Controls At Mode Changing/Start-Up

    Control Specification SiUS121632EA Controls at Mode Changing/Start-up 4.4.1 Preheating Control Outline The inverter operation in open phase starts with the conditions of the outdoor temperature and the preheating command from the indoor unit. Details ON Condition When the outdoor temperature is below 6°C (42.8°F), the inverter operation in open phase starts.
  • Page 97: Discharge Pipe Temperature Control

    SiUS121632EA Control Specification 4.4.5 Compressor Protection Function When turning the compressor from OFF to ON, the upper limit of frequency is set as follows. (The function is not used when defrosting.) (Hz) Frequency (sec.) Time (R13528) All outdoor units A (Hz) B (Hz) C (Hz) D (seconds)
  • Page 98: Input Current Control

    Control Specification SiUS121632EA Input Current Control Outline The microcomputer calculates the input current while the compressor is running, and sets the frequency upper limit based on the input current. In case of heat pump models, this control is the upper limit control of frequency and takes priority over the lower limit control of four way valve operation compensation.
  • Page 99: Freeze-Up Protection Control

    SiUS121632EA Control Specification Freeze-up Protection Control Outline During cooling operation, the signals sent from the indoor units control the operating frequency limitation and prevent freezing of the indoor heat exchanger. (The signals from the indoor units are divided into zones.) Details The operating frequency limitation is judged with the indoor heat exchanger temperature 2 seconds after operation starts and 30 seconds after the number of operation room is changed.
  • Page 100: Outdoor Fan Control

    Control Specification SiUS121632EA Outdoor Fan Control 1. Fan ON control to cool down the electrical box The outdoor fan is turned ON when the electrical box temperature is high while the compressor is OFF. 2. Fan OFF control during defrosting The outdoor fan is turned OFF while defrosting.
  • Page 101: Defrost Control

    SiUS121632EA Control Specification 4.11 Defrost Control Outline Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor heat exchanger temperature must be more than a certain value to finish defrosting. Details Conditions for Starting Defrost The starting conditions are determined with the outdoor temperature and the outdoor heat exchanger temperature.
  • Page 102: Low Hz High Pressure Limit

    Control Specification SiUS121632EA All outdoor units A (minutes) B (°C) 4 ~ 12 C (°F) 39.2 ~ 53.6 D (Hz) E (Hz) F (seconds) G (seconds) H (seconds) J (seconds) K (pulse) L (pulse) M (pulse) N (pulse) P (pulse) Q (pulse) 4.12 Low Hz High Pressure Limit Outline...
  • Page 103: Electronic Expansion Valve Control

    SiUS121632EA Control Specification 4.13 Electronic Expansion Valve Control Outline The following items are included in the electronic expansion valve control. Electronic expansion valve is fully closed 1. Electronic expansion valve is fully closed when turning on the power. 2. Pressure equalizing control Room Distribution Control 1.
  • Page 104 Control Specification SiUS121632EA Details The following are the examples of electronic expansion valve control which function in each operation mode. Operation pattern : Available — : Not available When power is turned on Fully closed when power is turned on —...
  • Page 105 SiUS121632EA Control Specification 4.13.1 Initialization as Power Supply On The electronic expansion valve is initialized (fully closed) when the power is turned on. Then, the valve opening is set and the pressure is equalized. 4.13.2 Pressure Equalizing Control When the compressor is stopped, the pressure equalizing control is activated. The electronic expansion valve opens and the pressure is equalized.
  • Page 106 Control Specification SiUS121632EA 4.13.8 Discharge Pipe Thermistor Disconnection Control Outline The disconnection of the discharge pipe thermistor is detected by comparing the discharge pipe temperature with the condensing temperature. If the discharge pipe thermistor is disconnected, the electronic expansion valve opens according to the outdoor temperature and the operation frequency, operates for a specified time, and then stops.
  • Page 107 SiUS121632EA Control Specification 4.13.10 SC (Subcooling) Control Outline The liquid pipe temperature and the heat exchanger temperature are detected and the electronic expansion valve opening is compensated so that the SC of each room becomes the target SC. When the actual SC is > target SC, open the electronic expansion valve of the room. When the actual SC is <...
  • Page 108: Malfunctions

    Control Specification SiUS121632EA 4.14 Malfunctions 4.14.1 Sensor Malfunction Detection Sensor malfunction may occur either in the thermistor or current transformer (CT) system. Relating to Thermistor Malfunction 1. Outdoor heat exchanger thermistor 2. Discharge pipe thermistor 3. Radiation fin thermistor 4. Gas pipe thermistor 5.
  • Page 109: Part 5 Remote Controller

    SiUS121632EA Part 5 Remote Controller 1. Applicable Remote Controller ..............98 2. ARC466A36 ....................99 3. ARC452A21 .................... 101 4. ARC452A23 .................... 103 5. ARC466A21 .................... 105 6. BRC1E73 (Wired Remote Controller) .............107 7. BRC082A41W, BRC082A42W(S) (Wireless Remote Controller Kit) ..113 Remote Controller...
  • Page 110: Applicable Remote Controller

    Applicable Remote Controller SiUS121632EA 1. Applicable Remote Controller Model Name Remote Controller Reference Page CTXG09QVJUW(S) ARC466A36 CTXG12QVJUW(S) CTXG18QVJUW(S) CTXS07LVJU ARC452A21 FTXS09LVJU FTXS12LVJU FTXS15LVJU FTXS18LVJU FDXS09LVJU ARC452A23 FDXS12LVJU CDXS15LVJU CDXS18LVJU FVXS09NVJU ARC466A21 FVXS12NVJU FVXS15NVJU FVXS18NVJU FFQ09Q2VJU Wired Remote Controller Wired Remote Controller...
  • Page 111: Arc466A36

    SiUS121632EA ARC466A36 2. ARC466A36 Signal transmitter Receiver 19-11/16” Display (LCD) (50 cm) or more • Displays the current settings. (In this illustration, each section is shown with all its displays on for the • To use the remote controller, aim the purpose of explanation.) transmitter at the indoor unit.
  • Page 112 ARC466A36 SiUS121632EA Open the Front Cover Mode button • Selects the operation mode. AUTO COOL HEAT Econo / Quiet button • Every time you press Econo/Quiet button, the setting changes in the following order. Lamp brightness ECONO OUTDOOR UNIT setting button QUIET •...
  • Page 113: Arc452A21

    SiUS121632EA ARC452A21 3. ARC452A21 Signal transmitter Receiver Display (LCD) • Displays the current settings. • To use the remote controller, aim the (In this illustration, each section is transmitter at the indoor unit. If there shown with all its displays on for the is anything to block signals between purpose of explanation.) the unit and the remote controller,...
  • Page 114 ARC452A21 SiUS121632EA Open the Front Cover MODE button • Selects the operation mode. AUTO COOL HEAT ECONO button • Starts ECONO operation. QUIET button SWING buttons • OUTDOOR UNIT QUIET • Adjusts the airflow direction. operation. • When you press SWING •...
  • Page 115: Arc452A23

    SiUS121632EA ARC452A23 4. ARC452A23 Signal transmitter Display (LCD) Receiver • Displays the current settings. • To use the remote controller, aim the (In this illustration, each section is transmitter at the indoor unit. If there shown with all its displays on for the is anything to block signals between purpose of explanation.) the unit and the remote controller,...
  • Page 116 ARC452A23 SiUS121632EA Open the Front Cover MODE button • Selects the operation mode. AUTO COOL HEAT ECONO button • Starts ECONO operation. QUIET button • OUTDOOR UNIT QUIET operation. SELECT button • OUTDOOR UNIT QUIET • Changes the ON/OFF TIMER operation is not available in FAN and DRY operation.
  • Page 117: Arc466A21

    SiUS121632EA ARC466A21 5. ARC466A21 Signal transmitter Display (LCD) • Displays the current settings. (In this illustration, each section is shown with all its displays on for the Receiver purpose of explanation.) Temperature • To use the remote controller, aim the transmitter at the indoor unit.
  • Page 118 ARC466A21 SiUS121632EA Open the Front Cover Mode button • Selects the operation mode. AUTO COOL HEAT Econo button • Starts ECONO operation. Quiet button Swing button • OUTDOOR UNIT QUIET • Adjusts the airflow direction. operation. • When you press Swing •...
  • Page 119: Brc1E73 (Wired Remote Controller)

    SiUS121632EA BRC1E73 (Wired Remote Controller) 6. BRC1E73 (Wired Remote Controller) 1. Operation mode selector button 11. LCD (with backlight) 4. Up button 5. Down button 6. Right button 7. Left button 9. Operation lamp 8. On/Off button 3. Menu/OK button 10.
  • Page 120 BRC1E73 (Wired Remote Controller) SiUS121632EA 1. Operation mode selector button 7. Left button • Press this button to select the operation • Used to highlight the next items on the mode of your preference. left-hand side. • * Available modes vary with the indoor unit Each screen is scrolled in the left-hand model.
  • Page 121 SiUS121632EA BRC1E73 (Wired Remote Controller) Liquid Crystal Display • Three types of display mode (Standard, Detailed and Simple) are available. • Standard display is set by default. • Detailed and Simple displays can be selected in the main menu. Standard display 10.Changeover controlled 11.Setback by the master indoor unit...
  • Page 122 BRC1E73 (Wired Remote Controller) SiUS121632EA Simple display 1.Operation mode 14.Selectable Display Item 3.Setpoint 11.Setback 2.Fan speed 4.Stand by for Defrost/ <Simple display example> Hot start Note for all display modes • Depending on the field settings, while the indoor unit is stopped, OFF may be displayed instead of the operation mode and/or the setpoint may not be displayed.
  • Page 123 SiUS121632EA BRC1E73 (Wired Remote Controller) “Error: Push Menu button” 1. Operation mode “Warning: Push Menu button” Used to display the current operation • • Displayed if an error or warning is detected. mode: Cool, Heat, Vent, Fan, Dry or Auto. In Auto mode, the actual operation mode •...
  • Page 124 BRC1E73 (Wired Remote Controller) SiUS121632EA 11. Setback “ ” • The setback icon flashes when the unit is turned on by the setback control. 12. Airflow Direction “ ” Displayed when the airflow direction and • swing are set. If the connected indoor unit model does not •...
  • Page 125: Brc082A41W, Brc082A42W(S) (Wireless Remote Controller Kit)

    SiUS121632EA BRC082A41W, BRC082A42W(S) (Wireless Remote Controller Kit) 7. BRC082A41W, BRC082A42W(S) (Wireless Remote Controller Kit) (R23936) (R23937) Remote Controller...
  • Page 126 BRC082A41W, BRC082A42W(S) (Wireless Remote Controller Kit) SiUS121632EA 11 TIMER MODE START/STOP BUTTON DISPLAY (SIGNAL TRANSMISSION) 12 TIMER RESERVE/CANCEL BUTTON This lights up when a signal is being 13 AIRFLOW DIRECTION ADJUST BUTTON transmitted. OPERATION MODE SELECTOR BUTTON DISPLAY Press this button to select OPERATION MODE. (OPERATION MODE) 15 FILTER SIGN RESET BUTTON This display shows the current OPERATION...
  • Page 127: Part 6 Service Diagnosis

    SiUS121632EA Part 6 Service Diagnosis 1. General Problem Symptoms and Check Items ........117 2. Troubleshooting with LED ...............118 2.1 Indoor Unit....................118 2.2 Outdoor Unit ..................... 120 3. Service Diagnosis ................... 121 3.1 CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series ........121 3.2 FFQ Series ....................
  • Page 128 SiUS121632EA 7.6 Outdoor Unit PCB Abnormality..............168 7.7 OL Activation (Compressor Overload) ............. 169 7.8 Compressor Lock ..................171 7.9 DC Fan Lock .................... 172 7.10 Input Overcurrent Detection ..............173 7.11 Four Way Valve Abnormality..............174 7.12 Discharge Pipe Temperature Control............176 7.13 High Pressure Control in Cooling .............
  • Page 129: General Problem Symptoms And Check Items

    SiUS121632EA General Problem Symptoms and Check Items 1. General Problem Symptoms and Check Items Reference Problem Symptom Check Item Details Page None of the units operates. Check the power supply. Check if the rated voltage is supplied. — Check the types of the indoor units. Check if the indoor unit type is compatible with —...
  • Page 130: Troubleshooting With Led

    Troubleshooting with LED SiUS121632EA 2. Troubleshooting with LED Indoor Unit Operation Lamp The operation lamp blinks when any of the following errors is detected. 1. When a protection device of the indoor or outdoor unit is activated, or when the thermistor malfunctions.
  • Page 131 SiUS121632EA Troubleshooting with LED FFQ series with wired remote controller (BRC1E73) Operation lamp (green) The error or warning message also blinks on the basic screen. (R23942) FFQ series with wireless remote controller kit (BRC082A41W, BRC082A42W(S)) In case of wireless remote controller, a transmitter board (A2P) and a receiver (A3P) are installed on indoor unit.
  • Page 132: Outdoor Unit

    Troubleshooting with LED SiUS121632EA Outdoor Unit The outdoor unit has a green LED (LED A) and red LEDs (LED 1 ~ LED 5) on the PCB. When the microcomputer works in order, the LED A blinks, and when the system is in normal condition, the red LEDs are OFF.
  • Page 133: Service Diagnosis

    SiUS121632EA Service Diagnosis 3. Service Diagnosis CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series 3.1.1 ARC452 Series Remote Controller 1. When TIMER CANCEL button is held down for 5 seconds, 00 is displayed on the temperature Method 1 display screen. TIMER CANCEL button <...
  • Page 134 Service Diagnosis SiUS121632EA Method 2 1. Press the 3 buttons (TEMP , TEMP , MODE) at the same time to enter the diagnosis mode. (R14550) The left-side number blinks. (R9430) 2. Press TEMP or TEMP button and change the number until you hear the two consecutive beeps or the long beep.
  • Page 135 SiUS121632EA Service Diagnosis 5. Press TEMP or TEMP button and change the number until you hear the long beep. (R14547) 6. Diagnose by the sound. beep : The left-side number does not correspond with the error code. two consecutive beeps : The left-side number corresponds with the error code but the right-side number does not.
  • Page 136 Service Diagnosis SiUS121632EA 3.1.2 ARC466 Series Remote Controller 1. When Timer Cancel button is held down for 5 seconds, 00 is displayed on the temperature Method 1 display screen. Timer Cancel button (R24045) < ARC466 Series > 2. Press Timer Cancel button repeatedly until a long beep sounds. The code indication changes in the sequence shown below.
  • Page 137 SiUS121632EA Service Diagnosis Method 2 1. Press the center of Temp button and Mode button at the same time. (R24046) is displayed on the LCD. (R11821) 2. Select 5C (service check) with Temp or Temp button. 3. Press Mode button to enter the service check mode. (R24047) The left-side number blinks.
  • Page 138 Service Diagnosis SiUS121632EA 5. Diagnose by the sound. beep: The left-side number does not correspond with the error code. two consecutive beeps: The left-side number corresponds with the error code but the right- side number does not. long beep: Both the left-side and right-side numbers correspond with the error code. The numbers indicated when you hear the long beep are the error code.
  • Page 139: Ffq Series

    SiUS121632EA Service Diagnosis FFQ Series 3.2.1 Wired Remote Controller (BRC1E73) Relations On power-up, the message Checking the connection. Please standby. will be displayed on the remote controller screen temporarily and then the basic screen will be displayed. To access a mode Between Modes from the basic screen, refer to the figure below.
  • Page 140 The error code will flash and the service Error Code: A1 Contact Info contact and model name or code may 0123-456-7890 be displayed. Indoor Model ---/000 Notify your Daikin dealer of the Error Outdoor Model ---/000 code and model name or code. Service Diagnosis...
  • Page 141 SiUS121632EA Service Diagnosis 3.2.2 Wireless Remote Controller Kit (BRC082A41W, BRC082A42W(S)) Relations The following modes can be selected by using INSPECTION/TEST OPERATION button on the remote controller. Between Modes Service data can be obtained. Indoor unit settings can be made. Press INSPECTION/TEST Error code history Filter cleaning sign time OPERATION button for...
  • Page 142 Service Diagnosis SiUS121632EA Step Action Press UP or DOWN button and change the UNIT No. until the receiver of the remote controller starts to beep. UP button DOWN button (R15408) If you hear... Then... 3 short beeps Follow all steps below. 1 short beep Follow steps 3 and 4.
  • Page 143 SiUS121632EA Service Diagnosis Step Action Press UP or DOWN button to change the error code upper digit until the indoor unit beeps. DOWN UP button DOWN button (R15411) If you hear... Then... 2 short beeps The upper digit matches. 1 short beep No digits match.
  • Page 144 Service Diagnosis SiUS121632EA Step Action Press UP or DOWN button and change the error code lower digit until the indoor unit generates long beep. DOWN UP button DOWN button (R15413) If you hear... Then... 2 short beeps No digits match. 1 long beep Both upper and lower digits match.
  • Page 145: Code Indication On Remote Controller

    SiUS121632EA Code Indication on Remote Controller 4. Code Indication on Remote Controller CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Error Codes Description Reference Page Normal condition — Indoor unit PCB abnormality Freeze-up protection control/heating peak-cut control DC motor (CTXG, CTXS, FTXS, FVXS series) Indoor fan motor or related abnormality AC motor (CDXS, FDXS series)
  • Page 146: Outdoor Unit

    Code Indication on Remote Controller SiUS121632EA Outdoor Unit : ON, : OFF, : Blinks Outdoor Unit LED Indication Error Reference Green Description Codes Page h 00 Normal condition — Unspecified voltage (between indoor unit and outdoor unit) Anti-icing control in other rooms (U0) Refrigerant shortage h U2...
  • Page 147: Troubleshooting For Ctxg, Ctxs, Ftxs, Cdxs, Fdxs, Fvxs Series

    SiUS121632EA Troubleshooting for CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series 5. Troubleshooting for CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Indoor Unit PCB Abnormality Error Code Method of Error The system checks if the circuit works properly within the microcomputer of the indoor unit. Detection Error Decision The system cannot set the internal settings.
  • Page 148 Troubleshooting for CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series SiUS121632EA Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Combination of the indoor and outdoor Match the compatible unit matched? models.
  • Page 149: Freeze-Up Protection Control/Heating Peak-Cut Control

    SiUS121632EA Troubleshooting for CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Freeze-up Protection Control/Heating Peak-cut Control Error Code Method of Error Freeze-up protection control During cooling operation, the freeze-up protection control (operation halt) is activated according Detection to the temperature detected by the indoor heat exchanger thermistor. Heating peak-cut control During heating operation, the temperature detected by the indoor heat exchanger thermistor is used for the heating peak-cut control (operation halt, outdoor fan stop, etc.)
  • Page 150: Indoor Fan Motor Or Related Abnormality

    Troubleshooting for CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series SiUS121632EA Indoor Fan Motor or Related Abnormality 5.3.1 Indoor Fan Motor (DC Motor) or Related Abnormality Applicable CTXG09/12/18QVJUW(S) CTXS07LVJU Models FTXS09/12/15/18/24LVJU FVXS09/12/15/18NVJU Error Code Method of Error The rotation speed detected by the Hall IC during indoor fan motor operation determines abnormal fan motor operation.
  • Page 151 SiUS121632EA Troubleshooting for CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check the power supply Check No.02 voltage. Refer to P.191 Is the voltage fluctuation...
  • Page 152 Troubleshooting for CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series SiUS121632EA 5.3.2 Indoor Fan Motor (AC Motor) or Related Abnormality Applicable FDXS09/12LVJU CDXS15/18LVJU Models Error code Method of Error The rotation speed detected by the Hall IC during indoor fan motor operation determines Detection abnormal fan motor operation.
  • Page 153 SiUS121632EA Troubleshooting for CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.04 Refer to P.191 Check the power supply voltage. Is the voltage fluctuation Correct the power supply.
  • Page 154: Thermistor Or Related Abnormality

    Troubleshooting for CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series SiUS121632EA Thermistor or Related Abnormality C4 , C9 Error Code Method of Error The temperatures detected by the thermistors determine thermistor errors. Detection Error Decision The voltage between the both ends of the thermistor is either 4.96 V or more, or 0.04 V or less with the power on.
  • Page 155: Front Panel Open/Close Fault

    SiUS121632EA Troubleshooting for CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Front Panel Open/Close Fault Applicable CTXG09/12/18QVJUW(S) Models Error Code Error Decision If the error repeats, the system is shut down. Conditions Supposed Defective reduction motor Malfunction or deterioration of the front panel mechanism Causes Defective limit switch Troubleshooting...
  • Page 156: Signal Transmission Error (Between Indoor Unit And Outdoor Unit)

    Troubleshooting for CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series SiUS121632EA Signal Transmission Error (Between Indoor Unit and Outdoor Unit) Error Code Method of Error The signal transmission data received from the outdoor unit is checked whether it is normal. Detection Error Decision The data sent from the outdoor unit cannot be received normally, or the content of the data is abnormal.
  • Page 157 SiUS121632EA Troubleshooting for CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.11 Check the power supply voltage. Refer to P.192 Is the voltage fluctuation Correct the power supply.
  • Page 158: Mismatching Of Indoor Unit And Outdoor Unit

    Troubleshooting for CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series SiUS121632EA Mismatching of Indoor Unit and Outdoor Unit Error Code Method of Error The supply power is detected for its requirements (pair type is different from multi type) by the indoor/outdoor transmission signal. Detection Error Decision The pair type and multi type are interconnected.
  • Page 159: Troubleshooting For Ffq Series

    SiUS121632EA Troubleshooting for FFQ Series 6. Troubleshooting for FFQ Series Indoor Unit PCB Abnormality Error Code Method of Error The system checks the data from EEPROM. Detection Error Decision The data from the EEPROM is not received correctly. Conditions EEPROM (Electrically Erasable Programmable Read Only Memory): A memory chip that holds its content without power.
  • Page 160: Drain Level Control System Abnormality

    Troubleshooting for FFQ Series SiUS121632EA Drain Level Control System Abnormality Error Code Method of Error The float switch detects error. Detection Error Decision The water level reaches its upper limit and the float switch turns OFF. Conditions Supposed Defective drain pump Causes Improper drain piping work Clogged drain piping...
  • Page 161: Indoor Fan Motor (Dc Motor) Or Related Abnormality

    SiUS121632EA Troubleshooting for FFQ Series Indoor Fan Motor (DC Motor) or Related Abnormality Error Code Method of Error The rotation speed detected by the Hall IC during indoor fan motor operation determines abnormal fan motor operation. Detection Error Decision The fan motor is not revved up. Conditions Supposed Layer short inside the fan motor winding...
  • Page 162 Troubleshooting for FFQ Series SiUS121632EA Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check the power supply voltage. Check No.02 Refer to P.191 Is the voltage fluctuation within Correct the power ±10% from the rated supply.
  • Page 163: Humidifier Or Related Abnormality

    SiUS121632EA Troubleshooting for FFQ Series Humidifier or Related Abnormality Error Code Method of Error Water leakage from humidifier(s) is detected based on the float switch ON/OFF changeover while the system is not operating. Detection Error Decision The float switch changes from ON to OFF while the system is OFF. Conditions Supposed Defective float switch...
  • Page 164: Thermistor Or Related Abnormality

    Troubleshooting for FFQ Series SiUS121632EA Thermistor or Related Abnormality C4 , C5 , C9 Error Code Method of Error The temperatures detected by the thermistors determine thermistor errors. Detection Error Decision The thermistor is disconnected or shorted while the unit is running. Conditions Supposed Disconnection of connector...
  • Page 165: Presence Sensor Or Floor Sensor Abnormality

    SiUS121632EA Troubleshooting for FFQ Series Presence Sensor or Floor Sensor Abnormality Error Code Method of Error The system detects abnormality by the output signal from the sensor(s). Detection Error Decision The sensor is disconnected or shorted while the unit is running. Conditions Supposed Disconnection of connector...
  • Page 166: Remote Controller Thermistor Abnormality

    Troubleshooting for FFQ Series SiUS121632EA Remote Controller Thermistor Abnormality Error Code Method of Error Even if remote controller thermistor is faulty, system is possible to operate by system thermistor. Malfunction detection is carried out by the temperature detected by the remote controller Detection thermistor.
  • Page 167: Signal Transmission Error (Between Indoor Unit And Outdoor Unit)

    SiUS121632EA Troubleshooting for FFQ Series Signal Transmission Error (Between Indoor Unit and Outdoor Unit) Error Code Method of Error The signal transmission data from the outdoor unit is checked whether it is normal. Detection Error Decision The data sent from the outdoor unit cannot be received normally, or the content of the data is abnormal.
  • Page 168 Troubleshooting for FFQ Series SiUS121632EA Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.11 Check the power supply voltage. Refer to P.192 Is the voltage fluctuation Correct the power supply. within ±10% from the rated value? Check the connection wires...
  • Page 169: Signal Transmission Error (Between Indoor Unit And Remote Controller)

    SiUS121632EA Troubleshooting for FFQ Series Signal Transmission Error (Between Indoor Unit and Remote Controller) Error Code Method of Error In case of controlling 1 indoor unit with 2 remote controllers, check the system using microcomputer if signal transmission between indoor unit and remote controller (main and sub) is normal. Detection Error Decision Normal transmission does not continue for specified period.
  • Page 170: Signal Transmission Error (Between Main Remote Controller And Sub Remote Controller)

    Troubleshooting for FFQ Series SiUS121632EA 6.10 Signal Transmission Error (Between MAIN Remote Controller and SUB Remote Controller) Error Code Method of Error In case of controlling 1 indoor unit with 2 remote controllers, check the system using microcomputer if signal transmission between MAIN remote controller and SUB remote controller is normal. Detection Error Decision Normal transmission does not continue for specified period.
  • Page 171: Mismatching Of Indoor Unit And Outdoor Unit

    SiUS121632EA Troubleshooting for FFQ Series 6.11 Mismatching of Indoor Unit and Outdoor Unit Error Code Error Decision Improper combination of indoor and outdoor units Conditions Supposed Defective indoor unit PCB Indoor-outdoor unit transmission wiring error Causes Defective optional unit(s) wirings Improper power supply wiring of indoor unit Improper wiring of connecting wires between indoor/outdoor units Troubleshooting...
  • Page 172: Troubleshooting For Outdoor Unit

    Troubleshooting for Outdoor Unit SiUS121632EA 7. Troubleshooting for Outdoor Unit Refrigerant Shortage Error Code Outdoor Unit LED Display Method of Error Refrigerant shortage is detected by checking the input current value and the compressor running frequency. If there is insufficient refrigerant, the input current tends to be lower than the normal Detection value.
  • Page 173 SiUS121632EA Troubleshooting for Outdoor Unit Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.01 Refer to P.190 Any thermistor Reconnect the thermistor(s). disconnected? ∗ Discharge pipe thermistor ∗...
  • Page 174: Low-Voltage Detection Or Over-Voltage Detection

    Troubleshooting for Outdoor Unit SiUS121632EA Low-voltage Detection or Over-voltage Detection Error Code Outdoor Unit LED Display Method of Error Indoor Unit Detection The zero-cross detection of the power supply is evaluated by the indoor unit PCB. Outdoor Unit Low-voltage detection: An abnormal voltage drop is detected by the DC voltage detection circuit.
  • Page 175 SiUS121632EA Troubleshooting for Outdoor Unit Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check the power supply voltage. Is the voltage fluctuation Correct the power supply. within ±10% from the rated value? Check the connection of the compressor harness.
  • Page 176: Wiring Error Check Unexecuted

    Troubleshooting for Outdoor Unit SiUS121632EA Wiring Error Check Unexecuted Error Code Outdoor Unit LED Display Method of Error The system checks if wiring error check is executed after clearing the memory. Detection Error Decision An error is determined when the unit is operated by the remote controller without executing wiring error check after the memory was cleared.
  • Page 177: Unspecified Voltage (Between Indoor Unit And Outdoor Unit)/Anti-Icing Control In Other Rooms

    SiUS121632EA Troubleshooting for Outdoor Unit Unspecified Voltage (Between Indoor Unit and Outdoor Unit)/Anti-icing Control in Other Rooms UA , UH Error Code Outdoor Unit LED Display Method of Error A wrong connection is detected by checking the combination of indoor and outdoor units on the microcomputer.
  • Page 178: Anti-Icing Control For Indoor Unit

    Troubleshooting for Outdoor Unit SiUS121632EA Anti-icing Control for Indoor Unit Error Code Outdoor Unit LED Display Method of Error During cooling operation, indoor unit icing is detected by checking the temperatures sensed by the indoor heat exchanger thermistor and room temperature thermistor that are located in a shut-down Detection room.
  • Page 179 SiUS121632EA Troubleshooting for Outdoor Unit Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.01 Refer to P.190 Check the wiring and piping. Check No.12 Wrong wiring or Activate the wiring error check piping? Refer to P.193...
  • Page 180: Outdoor Unit Pcb Abnormality

    Troubleshooting for Outdoor Unit SiUS121632EA Outdoor Unit PCB Abnormality Error Code Outdoor Unit LED Display Method of Error Detect within the program of the microcomputer. Detection Error Decision The program of the microcomputer is in abnormal running order. Conditions Supposed Defective outdoor unit PCB Causes Noise...
  • Page 181: Ol Activation (Compressor Overload)

    SiUS121632EA Troubleshooting for Outdoor Unit OL Activation (Compressor Overload) Error Code Outdoor Unit LED Display Method of Error A compressor overload is detected through compressor OL. Detection Error Decision If the error repeats, the system is shut down. Reset condition: Continuous run for about 60 minutes without any other error Conditions Supposed Disconnection of discharge pipe thermistor...
  • Page 182 Troubleshooting for Outdoor Unit SiUS121632EA Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.01 Refer to P.190 Discharge pipe thermistor Insert the thermistor in disconnected? position. Check No.12 Refer to P.193 Check No.
  • Page 183: Compressor Lock

    SiUS121632EA Troubleshooting for Outdoor Unit Compressor Lock Error Code Outdoor Unit LED Display Method of Error A compressor lock is detected by checking the compressor running condition through the position detection circuit. Detection Error Decision Judging from the current waveform generated when high-frequency voltage is applied to the compressor.
  • Page 184: Dc Fan Lock

    Troubleshooting for Outdoor Unit SiUS121632EA DC Fan Lock Error Code Outdoor Unit LED Display Method of Error An error is determined with the high-voltage fan motor rotation speed detected by the Hall IC. Detection Error Decision The fan does not start in 30 seconds even when the fan motor is running. If the error repeats, the system is shut down.
  • Page 185: Input Overcurrent Detection

    SiUS121632EA Troubleshooting for Outdoor Unit 7.10 Input Overcurrent Detection Error Code Outdoor Unit LED Display Method of Error Detected by checking the input current value Detection Error Decision The input current is at a certain value (depending on the condition) for 2.5 seconds. The compressor halts if the error occurs, and restarts automatically after 3-minute standby.
  • Page 186: Four Way Valve Abnormality

    Troubleshooting for Outdoor Unit SiUS121632EA 7.11 Four Way Valve Abnormality Error Code Outdoor Unit LED Display Method of Error The liquid pipe thermistor and the outdoor heat exchanger thermistor are checked to see if they function within their normal ranges in the operating mode. Detection Error Decision The following condition continues for A seconds after the compressor has started.
  • Page 187 SiUS121632EA Troubleshooting for Outdoor Unit Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.01 Refer to P.190 Four way valve coil Correct the four way valve disconnected (loose)? coil.
  • Page 188: Discharge Pipe Temperature Control

    Troubleshooting for Outdoor Unit SiUS121632EA 7.12 Discharge Pipe Temperature Control Error Code Outdoor Unit LED Display Method of Error An error is determined with the temperature detected by the discharge pipe thermistor. Detection Error Decision If the temperature detected by the discharge pipe thermistor rises above , the compressor stops.
  • Page 189: High Pressure Control In Cooling

    SiUS121632EA Troubleshooting for Outdoor Unit 7.13 High Pressure Control in Cooling Error Code Outdoor Unit LED Display Method of Error High pressure control (operation halt, frequency drop, etc.) is activated in cooling operation if the temperature sensed by the outdoor heat exchanger thermistor exceeds the limit. Detection Error Decision The temperature sensed by the outdoor heat exchanger thermistor rises above...
  • Page 190: Compressor Sensor System Abnormality

    Troubleshooting for Outdoor Unit SiUS121632EA 7.14 Compressor Sensor System Abnormality Error Code Outdoor Unit LED Display Method of Error The system checks the power supply voltage and the DC voltage before the compressor starts. The system checks the DC current of the compressor right after the compressor starts. Detection Power DC voltage...
  • Page 191 SiUS121632EA Troubleshooting for Outdoor Unit Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Turn off the power. Check the connection of the reactor. Connection OK? Connect the reactor properly.
  • Page 192: Position Sensor Abnormality

    Troubleshooting for Outdoor Unit SiUS121632EA 7.15 Position Sensor Abnormality Error Code Outdoor Unit LED Display Method of Error A compressor start-up failure is detected by checking the compressor running condition through the position detection circuit. Detection Error Decision If the error repeats, the system is shut down. Conditions Reset condition: Continuous run for about 5 minutes without any other error Supposed...
  • Page 193 SiUS121632EA Troubleshooting for Outdoor Unit Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.15 Turn off the power. Refer to P.195 Check the power supply voltage. Check No.18 Refer to P.197 Is the voltage fluctuation...
  • Page 194: Ct Or Related Abnormality

    Troubleshooting for Outdoor Unit SiUS121632EA 7.16 CT or Related Abnormality Error Code Outdoor Unit LED Display Method of Error A CT or related error is detected by checking the compressor running frequency and CT-detected input current. Detection Error Decision The compressor running frequency is more than Hz and input current is less than Conditions A (Hz)
  • Page 195 SiUS121632EA Troubleshooting for Outdoor Unit Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.15 Turn off the power. Then, turn on Refer to P.195 the power to restart the system. Check No.21 Start operation.
  • Page 196: Thermistor Or Related Abnormality (Outdoor Unit)

    Troubleshooting for Outdoor Unit SiUS121632EA 7.17 Thermistor or Related Abnormality (Outdoor Unit) H9 , J3 , J6 , J8 , J9 , P4 Error Code Outdoor Unit LED Display Method of Error This fault is identified based on the thermistor input voltage to the microcomputer. A thermistor fault is identified based on the temperature sensed by each thermistor.
  • Page 197 SiUS121632EA Troubleshooting for Outdoor Unit Troubleshooting In case of Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. Check No.01 Refer to P.190 Turn on the power again. Error displayed Reconnect the connectors again on remote or thermistors.
  • Page 198: Electrical Box Temperature Rise

    Troubleshooting for Outdoor Unit SiUS121632EA 7.18 Electrical Box Temperature Rise Error Code Outdoor Unit LED Display Method of Error An electrical box temperature rise is detected by checking the radiation fin thermistor with the compressor off. Detection Error Decision With the compressor off, the radiation fin temperature is above Conditions The error is cleared when the temperature drops below To cool the electrical components, the outdoor fan starts when the radiation fin temperature...
  • Page 199: Radiation Fin Temperature Rise

    SiUS121632EA Troubleshooting for Outdoor Unit 7.19 Radiation Fin Temperature Rise Error Code Outdoor Unit LED Display Method of Error A radiation fin temperature rise is detected by checking the radiation fin temperature with the compressor on. Detection Error Decision The radiation fin temperature with the compressor on is above The error is cleared when the temperature drops below Conditions 90°C (194°F)
  • Page 200: Output Overcurrent Detection

    Troubleshooting for Outdoor Unit SiUS121632EA 7.20 Output Overcurrent Detection Error Code Outdoor Unit LED Display Method of Error An output overcurrent is detected by checking the current that flows in the inverter DC section. Detection Error Decision A position signal error occurs while the compressor is running. A rotation speed error occurs while the compressor is running.
  • Page 201 SiUS121632EA Troubleshooting for Outdoor Unit Troubleshooting Be sure to turn off the power switch before connecting or disconnecting Caution connectors, or parts may be damaged. ∗ An output overcurrent may result from wrong internal wiring. If the system is interrupted by an output Check No.15 overcurrent after the wires have been disconnected and reconnected for part replacement, check the wiring again.
  • Page 202: Check

    Check SiUS121632EA 8. Check Thermistor Resistance Check Check No.01 Disconnect the connectors of the thermistors from the PCB, and measure the resistance of each thermistor using a multimeter. The data is for reference purpose only. Thermistor temperature Resistance (kΩ) °C °F –20 –4...
  • Page 203: Indoor Fan Motor Connector Check

    SiUS121632EA Check Indoor Fan Motor Connector Check Check No.02 CTXG, CTXS, FTXS, FVXS Series 1. Check the connection of connector. 2. Check motor power supply voltage output (pins 4 - 7). 3. Check motor control voltage (pins 4 - 3). 4.
  • Page 204: Power Supply Waveform Check

    Check SiUS121632EA Power Supply Waveform Check Check No.11 Measure the power supply waveform between No. 1 and No. 2 on the terminal board, and check the waveform disturbance. Check if the power supply waveform is a sine wave (Fig.1). Check if there is waveform disturbance near the zero-cross (sections circled in Fig.2) [Fig.1] [Fig.2] (R1444)
  • Page 205: Electronic Expansion Valve Check

    SiUS121632EA Check Electronic Expansion Valve Check Check No.12 Conduct the following to check the electronic expansion valve (EV). 1. Check if the EV connector is correctly inserted in the PCB. Match the EV unit number and the connector number. 2. Turn the power off and on again, and check if all the EVs generate a latching sound. 3.
  • Page 206: Four Way Valve Performance Check

    Check SiUS121632EA Four Way Valve Performance Check Check No.13 Turn off the power. Then, turn on the power to restart the system. ∗ Four way valve coil Start heating operation. Cooling/Dry/Defrost: Not energized Heating: energized voltage at 208 - 230 Replace the outdoor unit VAC with compressor PCB (main PCB).
  • Page 207: Inverter Analyzer Check

    SiUS121632EA Check Inverter Analyzer Check Check No.15 Characteristics Inverter analyzer: RSUK0917C If an abnormal stop occurs due to compressor startup failure or overcurrent output when using an inverter unit, it is difficult to judge whether the stop is caused by the compressor failure or some other failure (main PCB, power module, etc.).
  • Page 208: Rotation Pulse Check On The Outdoor Unit Pcb

    Check SiUS121632EA Diagnose method (Diagnose according to 6 LEDs lighting status.) (1) If all the LEDs are lit uniformly, the compressor is defective. → Replace the compressor. (2) If the LEDs are not lit uniformly, check the power module. → Refer to Check No.22. (3) If NG in Check No.22, replace the power module.
  • Page 209: Installation Condition Check

    SiUS121632EA Check 8.10 Installation Condition Check Check No.17 Installation condition check Check the allowable dimensions of the air Change the installation suction and location or direction. discharge area. Is the discharged air Change the installation short-circuited? location or direction. Is the outdoor heat Clean the outdoor heat exchanger very dirty? exchanger.
  • Page 210: Outdoor Fan System Check

    Check SiUS121632EA 8.12 Outdoor Fan System Check Check No.19 DC motor Check the outdoor fan system. Fan motor Is the lead wire connector outdoor fan running? Go to Check No. 16. disconnected? Reconnect the connector. Outdoor fan system is functioning. (R21195) 8.13 Main Circuit Short Check Check No.20...
  • Page 211: Capacitor Voltage Check

    SiUS121632EA Check 8.14 Capacitor Voltage Check Check No.21 Before this check, be sure to check the main circuit for short circuit. With the circuit breaker still on, measure the voltage according to the drawing of the model in question. Be careful never to touch any live parts. Multimeter (DC.
  • Page 212: Power Module Check

    Check SiUS121632EA 8.15 Power Module Check Check No.22 Check to make sure that the voltage between (+) and (–) of the power module is about 0 V before checking. Disconnect the compressor harness connector from the outdoor unit PCB. To disengage the connector, press the protrusion on the connector.
  • Page 213: Part 7 Trial Operation And Field Settings

    SiUS121632EA Part 7 Trial Operation and Field Settings 1. Pump Down Operation................202 2. Forced Cooling Operation ...............203 3. Wiring Error Check Function ..............204 4. Trial Operation ..................206 4.1 CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series ........206 4.2 FFQ Series ....................208 5.
  • Page 214: Pump Down Operation

    Pump Down Operation SiUS121632EA 1. Pump Down Operation Pump Down In order to protect the environment, be sure to conduct pump down operation when relocating or disposing of the unit. Operation 1. Remove the valve caps from the liquid stop valve and the gas stop valve. 2.
  • Page 215: Forced Cooling Operation

    SiUS121632EA Forced Cooling Operation 2. Forced Cooling Operation Outline The forced cooling operation is allowed when both the following conditions are met. 1. The outdoor unit is not abnormal and not in the 3-minute standby mode. 2. The outdoor unit is not operating. Protection functions have priority over all other functions during forced cooling operation.
  • Page 216: Wiring Error Check Function

    Wiring Error Check Function SiUS121632EA 3. Wiring Error Check Function Outline Wiring error check function is designed for the microcomputer to correct wiring errors itself. If local wiring is unclear in the case of buried piping, for example, just press the wiring error check switch on the outdoor unit.
  • Page 217 SiUS121632EA Wiring Error Check Function Details Refrigerant flows from Port A and on. The indoor heat exchanger temperatures are detected one by one to check up the matching between the piping and wiring. With this function on, freezing (crackling) noise may be heard from the indoor unit. This is not a problem.
  • Page 218: Trial Operation

    Trial Operation SiUS121632EA 4. Trial Operation CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Outline Carry out the trial operation in accordance with the operation manual to ensure that all functions and parts, such as flap movement, are working properly. Trial operation should be carried out in either cooling or heating operation. Procedure 1.
  • Page 219 SiUS121632EA Trial Operation ARC466 Series (1) Press On/Off button to turn on the system. (2) Press the center of Temp button and Mode button at the same time. (3) Select T (trial operation) with Temp or Temp button. (4) Press Mode button to start the trial operation. (5) Press Mode button and select operation mode.
  • Page 220: Ffq Series

    Trial Operation SiUS121632EA FFQ Series Outline Make sure to install the decoration panel before carrying out trial operation if the wireless remote controller is used. Trial operation should be carried out in either cooling or heating operation. 1. Measure the supply voltage and make sure that it is within the specified range. 2.
  • Page 221 SiUS121632EA Trial Operation With Wired Remote Controller (BRC1E73) 1. Set to COOL or HEAT operation using the Basic screen remote controller. Cool 2. Press and hold Cancel button for 4 seconds Set to Press and hold Cancel or longer. Service settings menu is button for 4 seconds or displayed.
  • Page 222 Trial Operation SiUS121632EA With Wireless Remote Controller Kit (BRC082A41W, BRC082A42W(S)) 1. Press button and select the COOL or HEAT operation. 2. Press button twice. “TEST” is displayed. 3. Press button within 10 seconds, and the test operation starts. Monitor the operation of the indoor unit for a minimum of 10 minutes. During test operation, the indoor unit will continue to cool/heat regardless of the temperature setpoint and room temperature.
  • Page 223: Field Settings

    SiUS121632EA Field Settings 5. Field Settings Outdoor Unit 5.1.1 Priority Room Setting Outline 1. Operation mode The operation mode of the prioritized room takes precedence. For example, when the prioritized indoor unit starts cooling operation, the other indoor units which have been in heating operation enter the standby mode.
  • Page 224 Field Settings SiUS121632EA 5.1.2 COOL/HEAT Mode Lock Use S15 connector to set the unit to cooling only or heating only. Setting to heating only (H): Short-circuit the pins 1 and 3 of the connector S15. Setting to cooling only (C): Short-circuit the pins 3 and 5 of the connector S15. The following specifications apply to the connector housing and pins.
  • Page 225: Ctxg, Ctxs, Ftxs, Cdxs, Fdxs, Fvxs Series

    SiUS121632EA Field Settings CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series 5.2.1 Model Type Setting ARC452A21, ARC452A23 The remote controller is common to the heat pump model and cooling only model. Make sure the DIP switch is set to the left side. The heating operation will not be available when the DIP switch is set to the right side.
  • Page 226 Field Settings SiUS121632EA 5.2.2 Temperature Display Switch You can select Fahrenheit or Celsius for temperature display. ARC452A21, ARC452A23 Press TEMP and TEMP buttons at the same time for 5 seconds to change the unit of temperature display. (R14477) ARC466A21, ARC466A36 Press the upper side of Temp button and On button at the same time for 5 seconds to change the unit of temperature display.
  • Page 227 SiUS121632EA Field Settings 5.2.3 When 2 Units are Installed in 1 Room Outline When 2 indoor units are installed in 1 room, 1 of the 2 indoor units and the corresponding wireless remote controller can be set for different address. Both the indoor unit PCB and the wireless remote controller need alteration.
  • Page 228 Field Settings SiUS121632EA CDXS, FDXS Cut the jumper JA on PCB. Series ADDRESS : JA EXIST (R22010) Caution Replace the PCB if you accidentally cut a wrong jumper. Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them. FVXS Series (1) Remove the front grille.
  • Page 229 SiUS121632EA Field Settings Wireless Remote (1) Remove the cover and take it off. Controller (2) Cut the address setting jumper. ARC452 series ARC466 series Jumper Jumper ADDRESS ADDRESS EXIST EXIST (R12065) ∗ Do not cut the left jumper. (R18416) Caution Replace the remote controller if you accidentally cut a wrong jumper.
  • Page 230: Ffq Series

    Field Settings SiUS121632EA FFQ Series 5.3.1 How to Change the Field Settings Outline If optional accessories are mounted on the indoor unit, the indoor unit setting may have to be changed. Refer to the instruction manual for each optional accessory. Note: When using 2 remote controllers for 1 indoor unit, change the field settings from MAIN remote controller.
  • Page 231 SiUS121632EA Field Settings 3. Highlight the mode, and select desired “Mode No.” by using (Up/Down) button. 4. In the case of setting per indoor unit during group control (When Mode No. such as 20 22 23 25 are selected), highlight the unit No.and select “Indoor unit No.” to be set by using (Up/Down) button.
  • Page 232 Field Settings SiUS121632EA Wireless Remote Controller Kit (BRC082A41W, BRC082A42W(S)) UP button Mode No. Field setting mode DOWN button First code No. RESERVE button MODE button Second code No. INSPECTION/TEST button (R24061) To set the field settings, you have to change: Mode No.
  • Page 233 SiUS121632EA Field Settings 5.3.2 Overview of the Field Settings First Second Code No. Mode Code Description of setting Approx. Approx. Filter cleaning Longlife 2,500 1,250 — — — — sign interval filter hrs. hrs. (20) Remote controller thermistor Enabled Disabled —...
  • Page 234 Field Settings SiUS121632EA 5.3.3 MAIN/SUB Setting when Using 2 Wired Remote Controllers Outline The MAIN/SUB setting is necessary when 1 indoor unit is controlled by 2 remote controllers. When you use 2 remote controllers, set one to MAIN and the other to SUB. Details 1.
  • Page 235 SiUS121632EA Field Settings 5.3.4 Address and MAIN/SUB Setting for Wireless Remote Controller Outline If setting multiple wireless remote controllers to operate in one room, perform address setting for the receiver and the wireless remote controller. If using both a wired remote controller and a wireless remote controller with 1 indoor unit, change the MAIN/SUB switch of the transmitter board.
  • Page 236 Field Settings SiUS121632EA Wireless Remote Factory set is 1. Change the wireless remote controller address setting by the following steps, if Controller necessary. 1. Hold down button and /TEST button at the same time for at least 4 seconds to enter the Address field setting mode.
  • Page 237 SiUS121632EA Field Settings After Setting Affix corresponding unit number labels onto both air outlet of the decoration panel and onto back of the wireless remote controller. (R24066) Note: Set the unit No. of the receiver and the wireless remote controller to be the equal. If the settings differ, the signal from the remote controller cannot be transmitted.
  • Page 238: Silicone Grease On Power Transistor/Diode Bridge

    Silicone Grease on Power Transistor/Diode Bridge SiUS121632EA 6. Silicone Grease on Power Transistor/Diode Bridge Outline Apply the specified silicone grease to the heat radiation part of a power transistor/diode bridge when you replace an outdoor unit PCB. The silicone grease encourages the heat radiation of a power transistor/diode bridge.
  • Page 239: Part 8 Appendix

    SiUS121632EA Part 8 Appendix 1. Piping Diagrams..................228 1.1 Indoor Unit....................228 1.2 Outdoor Unit ..................... 231 2. Wiring Diagrams..................232 2.1 Indoor Unit....................232 2.2 Outdoor Unit ..................... 238 3. Operation Limit..................240 Appendix...
  • Page 240: Piping Diagrams

    Piping Diagrams SiUS121632EA 1. Piping Diagrams Indoor Unit CTXG09/12QVJUW(S) CTXG18QVJUW(S) Indoor unit Indoor unit Heat exchanger thermistor Heat exchanger thermistor 1/4 CuT 1/4 CuT Heat exchanger Heat exchanger Crossflow fan Crossflow fan Field piping Field piping 1/4 CuT 1/4 CuT Fan motor Fan motor Field piping...
  • Page 241 SiUS121632EA Piping Diagrams FDXS09/12LVJU CDXS15/18LVJU INDOOR UNIT INDOOR UNIT (1/4CuT) (1/4 (6.4mm) CuT) HEAT EXCHANGER HEAT EXCHANGER THERMISTOR ON HEAT EXCH. THERMISTOR FIELD PIPING FIELD PIPING ON HEAT (1/4CuT) SIROCCO FAN (1/4 (6.4mm) CuT) SIROCCO FAN EXCH. FAN MOTOR FAN MOTOR FIELD PIPING (3/8CuT) FIELD PIPING...
  • Page 242 Piping Diagrams SiUS121632EA FFQ09/12/15/18Q2VJU REFRIGERANT FLOW COOLING HEATING HEAT EXCHANGER LIQUID PIPE CONNECTION PORT φA GAS PIPE CONNECTION PORT φB MODEL FFQ09Q2VJU 1/4 (6.4) 3/8 (9.5) FFQ12Q2VJU 1/2 (12.7) FFQ15Q2VJU FFQ18Q2VJU 4D106033 Appendix...
  • Page 243: Outdoor Unit

    SiUS121632EA Piping Diagrams Outdoor Unit 2MXL18QMVJU OUTDOOR UNIT ELECTRONIC LIQUID PIPE HEAT EXCHANGER EXPANSION VALVE THERMISTOR OUTDOOR AIR 1/4 CuT 5/16 CuT 5/16 CuT HEADER THERMISTOR ROOM A (1/4 CuT) FIELD FILTER PIPING 5/16 CuT 1/4 CuT LIQUID 5/16 CuT ROOM B HEAT EXCHANGER (1/4 CuT)
  • Page 244: Wiring Diagrams

    Wiring Diagrams SiUS121632EA 2. Wiring Diagrams Indoor Unit CTXG09/12/18QVJUW(S) Wiring diagram : Frame ground : Signal receiver F1U, F2U : Fuse : Ground OUTDOOR H1P, H2P : Pilot lamp H1-H3 : Harness GRN/YLW R1T, R2T : Thermistor MR10 : Magnetic relay S25-S200 : Connector : Varistor...
  • Page 245 SiUS121632EA Wiring Diagrams CTXS07LVJU, FTXS09/12LVJU PCB3 PCB1 LED1 OUTDOOR 3.15A C102 LED2 MR10 FIELD WIRING. LED3 C101 GRN/YLW TRANSMISSION CIRCUIT CAUTION NOTE THAT OPERATION WILL RESTART AUTOMATICALLY IF THE MAIN POWER SUPPLY IS TURNED OFF AND THEN BACK ON AGAIN. t˚...
  • Page 246 Wiring Diagrams SiUS121632EA FTXS15/18LVJU WIRING DIAGRAM PCB3 PCB1 LED1 OUTDOOR 3.15A C102 LED2 MR10 FIELD WIRING. LED3 C101 GRN/YLW TRANSMISSION CIRCUIT CAUTION NOTE THAT OPERATION WILL RESTART AUTOMATICALLY IF THE MAIN POWER SUPPLY IS TURNED OFF AND THEN BACK ON AGAIN. t˚...
  • Page 247 SiUS121632EA Wiring Diagrams FDXS09/12LVJU, CDXS15/18LVJU → V1TR 3.15A OUTDOOR LED LED GRN/YLW FIELD WIRING. TERMINAL FOR CAUTION TRANSMISSION CENTRALIZED CONTROL CIRCUIT NOTE THAT OPERATION WILL RESTART AUTOMATICALLY IF THE MAIN POWER SUPPLY IS TURNED OFF AND THEN BACK SIGNAL ON AGAIN. RECEIVER RTH1 H1P~H3P...
  • Page 248 Wiring Diagrams SiUS121632EA FVXS09/12/15/18NVJU PCB3 PCB2 → RECTIFIER S2W ( 4 ) 3.15A OUTDOOR GRN/YLW MR10 FIELD WIRING. WIRELESS TRANSMISSION REMOTE CIRCUIT CAUTION CONTROLLER PCB4 NOTE THAT OPERATION WILL SIGNAL RESTART AUTOMATICALLY IF RECEIVER THE MAIN POWER SUPPLY IS TURNED OFF AND THEN BACK LED2 LED1 3.15A...
  • Page 249 SiUS121632EA Wiring Diagrams FFQ09/12/15/18Q2VJU INDOOR UNIT PILOT LAMP (ON-RED) PRINTED CIRCUIT BOARD PILOT LAMP WIRING DIAGRAM WIRELESS REMOTE CONTROLLER C105 (TIMER-GREEN) CAPACITOR (M1F) (RECEIVER/DISPLAY UNIT) DIP SWITCH ON PCB PILOT LAMP (OPTIONAL ACCESSORY) FUSE (F, 5A, 250V) (FILTER SIGN-RED) FLASHING LAMP PILOT LAMP (SERVICE MONITOR GREEN) (DEFROST-ORANGE)
  • Page 250: Outdoor Unit

    Wiring Diagrams SiUS121632EA Outdoor Unit 2MXL18QMVJU WIRING DIAGRAM GRN/YLW PCB2 POWER SUPPLY S501 S502 TO INDOOR UNIT X11A ROOM B PCB1 S201 S202 TO INDOOR UNIT ROOM A MRM20 MRM10 3.15A V401 3.15A C110 IPM1 ROOM A ROOM B t˚ t˚...
  • Page 251 SiUS121632EA Wiring Diagrams 3MXL24QMVJU WIRING DIAGRAM GRN/YLW PCB2 POWER SUPPLY S501 S502 TO INDOOR UNIT X11A ROOM B PCB1 1 S202 S201 TO INDOOR UNIT ROOM A MRM20 MRM10 TO INDOOR UNIT ROOM C 3.15A W V U V401 3.15A C110 IPM1 ROOM A...
  • Page 252: Operation Limit

    Operation Limit SiUS121632EA 3. Operation Limit 2MXL18QMVJU, 3MXL24QMVJU Heating Cooling 114.8 60/75.2 41/42.8 -13/-13 57.2/68 73.4/89.6 82.4/98.6 Indoor temp. (˚FWB/˚FDB) Notes: Indoor temp. (˚FDB) The graphs are based on the following conditions. • Equivalent piping length 25ft • Level difference 3D101428 •...
  • Page 253 Revision History Month / Year Version Revised contents 09 / 2016 SiUS121632E First edition 03 / 2017 SiUS121632EA Model addition: FFQ18Q2VJU...
  • Page 254 Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorized parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.