SiUS181305E

7.10 INTELLIGENT EYE Operation

Outline
CTXS, FTXS Series
This function detects the existence of humans in the room with a motion sensor (INTELLIGENT
EYE) and reduces the capacity when there is nobody in the room in order to save electricity.
Detail
1. Detection method by INTELLIGENT EYE
 This sensor detects human motion by receiving infrared rays and displays the pulse wave
 The microcomputer in the indoor unit carries out a sampling every 20 msec. and if it detects 10
2. The motions (for example: in cooling)
Human detection
signal
Target temperature
Remote controller
INTELLIGENT
EYE button
Operation
Fan speed ()
 When the microcomputer does not have a signal from the sensor in 20 minutes, it judges that
 In FAN operation, the fan speed is reduced by 50 ~ 60 rpm.
 For dry operation, you cannot set the temperature with a remote controller, but the target
Others
Function
sampling (20 msec.)
High
Sensor output
Low
(Human motion)
ON
Human detection
signal
OFF
output.
cycles of the wave in 1 second in total (corresponding to 20 msec. × 10 = 200 msec.), it judges
humans are in the room as the motion signal is ON.
within 20 min.
ON
OFF
RESET.
ON
OFF
ON
OFF
OFF
nobody is in the room and operates the unit at a temperature shifted from the target
temperature. (Cooling / Dry: 1 ~ 2°C (1.8 ~ 3.6°F) higher, Heating: 2°C (3.6°F) lower, Auto:
according to the operation mode at that time.)
temperature is shifted internally.
Function of CTXS, FTXS, CDXS, FDXS Series
20 min.
Set speed
If the sensor detects the outputs
10 times/sec. or more, it judges
humans exist.
1 sec.
20 min.
Set speed
(R2821)