Daikin RMXS-L Series Service Manual page 111

Multi-split 8-zone heat pump systems
Hide thumbs Also See for RMXS-L Series:
Table of Contents

Advertisement

SiUS181305E
Push the BS2 (SET button) and match with the LEDs No. 1 - 15, push the BS3 (RETURN button),
and confirm the data for each setting.
 Data such as addresses and number of units is expressed as binary numbers; the two ways of
expressing are as follows:
 Refer to the preceding page for a list of data, etc. for No. 0 - 25.
2.1.2 COOL/HEAT Changeover Setting by Dip Switches
The following field settings are made by dip switches on the service PCB.
DS1-1
DS1-2
Test Operation and Field Settings
Figure 1
l h l h l l h
16
4
1
32
8
2
(R12951)
Figure 2
l h h h l h l
64 16
No.12
128 32
l h h h l l h
4
1
No.13
8
2
(R12952)
Dip switch
No.
Setting
ON (OUT)
OFF (IN) (Factory
setting)
ON
OFF (Factory setting)
The No. 1 cool / heat unified address is expressed as a binary
number consisting of the lower 6 digits. (0 - 63)
In the figure 1, the address is 010110 (binary number), which
translates to 16 + 4 + 2 = 22 (base 10 number). In other words, the
address is 22.
The number of terminal blocks for No. 12 and 13 is expressed as an
8-digit binary number, which is the combination of four upper, and
four lower digits for No. 12 and 13 respectively. (0 - 128)
In the figure 2, the address for No. 12 is 0101, the address for No. 13
is 0110, and the combination of the two is 01010110 (binary number),
which translates to 64 + 16 + 4 + 2 = 86 (base 10 number). In other
words, the number of terminal block is 86.
Setting item
Cool / Heat
It is used for changing over the unit which inputs the
changeover
COOL/HEAT switching command.
setting
Not used
Do not change the factory settings.
Field Settings
Description
102

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents