Setting of Demand Operation
By connecting the external contact input to the demand input of the outdoor unit external control
adaptor (optional), the power consumption of unit operation can be saved suppressing the
compressor operating condition.
Demand
When the constant demand operation is carried out. (Use of the external control adaptor for
outdoor unit is not required.)
1. While in setting mode 2, make setting of the set item No. 32 (Setting of constant demand) to
2. While in setting mode 2, select the set item No. 30 (Setting of Demand 1 level) and then set the
Image of operation
Power consumption
Rated power consumption
80 % of rated power consumption
70 % of rated power consumption
60 % of rated power consumption
Test Operation and Field Settings
Set item
Condition
Mode 1
Mode 2
Mode 3
ON.
setting condition to targeted mode.
The power consumption set with Demand 1 level setting.
Content
The compressor operates at approx. 60% or less of rating.
The compressor operates at approx. 70% or less of rating.
The compressor operates at approx. 80% or less of rating.
Field Settings
When the
Constant demand
setting is set to ON
(OFF has been set at
factory.) , the power
consumption can be
set with the Demand 1
level setting. (70 % of
rated power
consumption has been
set at factory.)
(R19196)