Radiation Fin Thermistor Abnormality - Daikin RMXS-L Series Service Manual

Multi-split 8-zone heat pump systems
Hide thumbs Also See for RMXS-L Series:
Table of Contents

Advertisement

SiUS181305E

7.23 Radiation Fin Thermistor Abnormality

P4
Error Code
Method of Error
Resistance of radiation fin thermistor is detected when the compressor is not operating.
Detection
Error Decision
When the resistance value of thermistor becomes a value equivalent to open or short circuited
Conditions
status
 Malfunction is not decided while the unit operation is continued.
 Defective radiation fin thermistor (FINTH)
Supposed
 Defective main PCB (A1P)
Causes
Troubleshooting
Power OFF
Power ON
Refer to Thermistor Resistance / Temperature Characteristics table 2 on page 225.
Troubleshooting
P4
is displayed by pressing the inspection button.
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Is the
resistance of the
radiation fin thermistor
normal?
Disconnect the lead wires
from the compressor, and
then check the compressor
for the insulation resistance.
The
insulation
resistance is low. (not
more than 100
kΩ)
Remove and insert the
connector for the radiation
fin thermistor X111A.
Turn
ON the power
supply, and then check
whether or not the
malfunction
recurs.
NO
YES
YES
NO
YES
NO
Troubleshooting for Outdoor Unit
Replace the radiation fin
thermistor.
Replace the compressor.
Replace the main PCB
(A1P).
Completed.
(R17943)