SiUS181305E
7.30 Transmission Error between Centralized Remote
Controller and Indoor Unit
UE
Error Code
Method of Error
Microcomputer checks if transmission between indoor unit and centralized remote controller is
Detection
normal.
Error Decision
When transmission is not carried out normally for a certain amount of time
Conditions
Transmission error between optional controllers for centralized control and indoor unit
Supposed
Connector for setting master controller is disconnected.
Causes
Defective PCB of centralized remote controller
Defective indoor unit PCB
Troubleshooting
Troubleshooting for Outdoor Unit
216