Configuration manual
• Input parameters
- Mode, determines the type of event generated by
activation of the input.
- Group activated, indicates the group that will activate
following input activation.
- Prealarm, determines when activation of the input will
start the associated prealarm time.
The possible values are: "Never", "In day mode" and
"Always".
- Resettable, where present, if activated, the event
generated by the activation of the input will reset when
the terminal resets.
• Output parameters
- Type, determines the way in which the output will be
conditioned by bypass and silence operations by type
- Group activating the output, group whose activation
determines the activation of the output
- Silenceable, if selected, once the output is activated it
can be deactivated by silencing the control panel
- Pattern, pressing this button accesses the successive
screen, which allows you to set the activation pattern
for each output status.
The available output statuses are "Stand-by", "Warning",
"Prealarm" and "Alarm".
4.2

Parameters of control panel terminals

It is possible to set the parameters of an "I/O" terminal only after the line has been configured and the type of device
connected to it specified (paragraph 3.6). The programming of the parameters varies according to the specified choice.
The parameters of each device connected to the terminals on-board the control panel (I/O lines and relays) can be
reached in two ways:
- via the "Configuration menu", selecting the section relative to the terminal shows the section
with the list of terminals.
- via the "Modify" menu and pressing the I/O Lines button.
Two pages will be displayed, navigable with the arrow keys, with a list of all the configured devices
and their statuses.
The Program button is available for each terminal and allows access to the input/output programming menu:
• General settings
- Description, label that identifies the individual point and
which is shown in the events it is involved in.
- Zone, geographic group the point belongs to
- Use Zone Group, if this box is selected, the point in
question will be assigned to the default group
associated with the zone selected at the previous step
(if this is already the assigned group, the box will be
selected automatically when this screen is displayed)
Parameters of devices and their groupings
Alarm
Generic alarm
Group activated
Always
Prealarm
Access
level:3
Alarm
Group activating
Generic alarm
the output
Silenceable
Pattern
Access
level:3
General Alarm
Description
Room
Zone
Use Zone Group
Access
level:3
Mode
Esc
Set
Type
Esc
Set
Esc
Set
23