The Previdia Compact control panel has pre-configured default output groups with specific extinction functions:
Outputs group
3
Extinguishing
Pre-
4
Extinguishing
Automatic
5
Exting.
Manual Exting.
6
Manual Stop
7
Stop By Device
8
Disab. Aut.
9
Exting.
Exting. Fault
10
Activate Exting.
11
EN12094-1:
The previous groups can be associated with supervised outputs connected to other devices, internal or
external to the fire extinguishing system, thus creating options 4.24 "Triggering signals to equipment
within the system" and 4.26 "Triggering of the equipment outside the system" of standard EN 12094-1.
3.10
Setting the date and time
Proceed with the time and date setting by selecting the time
and date pane in the lower-right corner of the start page [B]
and, after entering an access code, set the individual fields
using the scroll arrows.
20
Activation
Group that activates the release of the gas.
Group that goes into prealarm status during the
pre-extinction time and into alarm status during
the release phase.
Group that activates during pre-extinction and
release conditions, if they are triggered by
automatic activations (e.g. two alarms in a
specific zone).
Group that activates during pre-extinction and
release conditions, if they are triggered by
inputs programmed for manual extinction
activation.
Group that follows the activation of inputs
programmed as "Stop extinction Abort", "Stop
extinction Hold" or "Stop extinction Add".
Group that follows the activation of the inputs
programmed as "Stop extinction External".
Group that activates in the event of the
disabling of automatic activation (e.g. two
alarms in a specific zone) of extinction
Group that is activated in the event of a fault on
any component of the system with extinction
functions (an extinction input or an output set
as "Fire Protection System").
Group whose activation starts the automatic
pre-extinction time count.
Fire detection and extinguishant system
EN 12094-1
By programming a different
tone pattern (or sound) for the
prealarm and alarm conditions
of an output associated with
this group, this output will
implement option 4.30
("Activation of alarm devices
with different signals ").
Options 4.27 "Emergency
abort device" and 4.20
"Emergency hold device"
4.19 "Monitoring of the status
of components"
4.19 "Monitoring of the status
of components"
Access
level:1
Associated
extinction
function
Release
Pre-Extinguishing
Log
C
System status
Programming
B
01/01/2018 18:23
System Parameters
Need help?
Do you have a question about the Previdia Compact and is the answer not in the manual?