Starting/Stopping; Load Default; Firmware Version Checking - Sungrow SG2500-MV System Manual

Mv turnkey station
Table of Contents

Advertisement

System Manual
9.10

Starting/Stopping

Usually, the inverter will start automatically when the grid-connected
requirements are met.
Follow either of the two ways below to start/stop the inverter through the LCD screen:
Tap "Start/Stop" from the default menu.
Tap "Start/Stop" from the Function menu.
Start or stop the inverter by tapping the start/stop button on the screen.
A confirm operation interface will appear after tapping the corresponding buttons. The
instruction is effective after confirmation; cancel the operation by tapping "Cancel".
9.11

Load Default

Proceed as follows to perform the load default:
Tap "Function" from the default menu;
Step 1
Tap "Set-parameter";
Step 2
Tap "Sys-parameter" after entering the correct password;
Step 3
Tap "Load default" and the password inputting window appears;
Step 4
The password is "1111". The system will be reset after entering the password.
9.12

Firmware Version Checking

User can view the firmware version of LCD and DSP as follows:
Tap "Function" from the default menu;
Step 1
Tap "Set-parameter";
Step 2