Analog Input
As an alternative to the pulse inputs, the Series 3000 flow monitor can accept an Analog input . The input is non-isolated, but
can accept 0...1V DC, 0...5V DC, 0...10V DC, 0...20 mA and 4...20 mA with both factory-defined and custom units
of measure .
Low impedance 100 Ohm input for current inputs optimizes performance and flexibility or loop power supplies . Both the
low-end and high-end scaling are independent and field configured by the installer .
N
OTEE:
See
"Programming Flowchart—Software Version 1.2.29" on page 13
April 2017
Figure 5: Data industrial flow sensor wiring examples (two- and three-wire pulse types)
Figure 6: 4...20 mA analog loop powered wiring
Figure 7: Voltage or current sourcing analog inputs
DSY-UM-01667-EN-05
1 ANALOG IN+
2 ANALOG IN-
3 SHIELD
4 SENSOR IN
5 GND
6 SHIELD
7 SENSOR PWR
for required input configuration .
1 ANALOG IN+
2 ANALOG IN-
3 SHIELD
4 SENSOR IN
5 GND
6 SHIELD
7 SENSOR PWR
1 ANALOG IN+
2 ANALOG IN-
3 SHIELD
4 SENSOR IN
5 GND
6 SHIELD
7 SENSOR PWR
Installation
Page 7