Output Option Card

OUTPUT OPTION CARD
If the Series 3000 flow monitor was ordered with the Output Option card, it will have these additional outputs:
Analog Output (0...20 mA; or 4...20 mA), which can be converted externally to 0...5V DC, 1...5V DC with a 250 Ohm
resistor, or 0...10V DC or 2...10V DC with a 500 Ohm resistor . A 15V DC power supply is provided to permit current sinking
or sourcing . The Series 3000 flow monitor has special software that permits the analog output .
USB for direct access to a computer using a standard mini-USB cable .
RS485 for fully addressable Modbus or BACnet communication .

USB Port

To communicate using the USB port requires Windows® HyperTerminal or other similar communications software . This port is
part of the Analog Output Option card . See
Page 10
1 RS485 B
2 RS485 A
3 RS485 GND
4 LOOP +
5 LOOP -
6 GND
Figure 11: Current sourcing analog output
1 RS485 B
2 RS485 A
3 RS485 GND
4 LOOP +
5 LOOP -
6 GND
Figure 12: Current sinking analog output
1 RS485 B
2 RS485 A
3 RS485 GND
4 LOOP +
5 LOOP -
6 GND
Figure 13: Analog output wiring
"Communication" on page 19
DSY-UM-01667-EN-05
+
-
for instructions on how to use this port .