Parameter Window "Output - ABB i-bus EIB/KNX AA/S 4.1 Product Manual

Analogue actuator,analogue actuator module. intelligent installation systems
Table of Contents

Advertisement

ABB i-bus
EIB / KNX
®
4.2.3
Parameter window
"Output X 2/2"
Commissioning
Fig. 9: Parameter window "Output X 2/2"
Forced control object 1
Forced control object 2
Options:
– not existing
– forced control active at "1" telegram
– forced control active at "0" telegram
Both forced control objects enable the control of an output with a higher
priority than the 1-byte or 2-byte input object.
If this parameter is set to "not existing" the ETS will not display the
corresponding 1-bit object. If the object is used, this parameter will
determine at which object value forced control is active. If the forced
control object is deactivated, the output will assume the value in
accordance with the "Input value" object.
If both forced control objects are active, forced control object 1 has the
higher priority.
Forced control active at 1 or 0 telegram: The parameters "Output value in
case of forced control 1 or 2 in %" are displayed.
Output value with forced control 1 in %
Output value with forced control 2 in %
Options:
– 0...100 (50)
This parameter determines the output value if the corresponding forced
control object is active.
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

I-bus eib/knx aam/s 4.1

Table of Contents