Dimension Drawing; Installation - ABB i-bus EIB/KNX AA/S 4.1 Product Manual

Analogue actuator,analogue actuator module. intelligent installation systems
Table of Contents

Advertisement

ABB i-bus
EIB / KNX
®
3.1.2

Dimension drawing

3.1.3

Installation

8
Device Technology
Analogue Actuator Module AAM/S 4.1
Fig. 6: Analogue Actuator Module AAM/S 4.1
The connection to the Analogue Actuator will by carried out via a 6-pole
system connector (supplied with the Analogue Actuator Module).
A maximum of one Analogue Actuator Module can be connected.
An Analogue Actuator Module can be replaced while the system is in opera-
tion (disconnect voltage supply from module!). After the replacement, the
Analogue Actuator makes a reset after approx. 25 s. This action reinitialises
all outputs of the Analogue Actuator and resets them to their original state.
Removal or addition of modules without adapting the project and
subsequent downloading into the Analogue Actuator is not permitted
as this will result in system malfunctions.
¼
Do not connect electronic ballast's or electronic transformers
with 1 – 10 V control input to the outputs!
¼
Do not connect external voltages to the outputs.
Connected components must ensure safe separation from
other voltages.
¼
The 0 V terminals must not be connected with the terminals
of the same designation of an Analogue Actuator (risk of
irreparable damage!).
¼
The 0 V terminals of outputs A5...A8 are internally connected.

Advertisement