Technical Data - ABB i-bus EIB/KNX AA/S 4.1 Product Manual

Analogue actuator,analogue actuator module. intelligent installation systems
Table of Contents

Advertisement

ABB i-bus
EIB / KNX
®
3
Device technology
AAM/S 4.1
Fig. 4: AAM/S 4.1
3.1

Technical Data

Power supply
Outputs
Output current
Operating and display elements
Connections
Enclosure
Ambient temperature range
Humidity
Design
Housing, colour
Installation
Dimensions
Mounting depth / width
Weight
Mounting position
Approvals
CE mark
6
Device Technology
Analogue Actuator Module AAM/S 4.1
The Analogue Actuator Module expands the Analogue Actuator AA/S 4.1
by four analogue outputs. The device converts measured data received via
the EIB / KNX to analogue output signals. The analogue outputs can be
used as current or voltage outputs with adjustable output signals.
The Analogue Actuator Module is a DIN rail device for installation in the
distribution board. For operation the 24 V AC power supply can be carried
out by AA/S 4.1.
Operating voltage
Current consumption
Current consumption on system connector
4 analogue outputs
Signal type
Output signal load
Voltage signal
Current signal
Device status display
Output signal A5...A8 display
Analogue outputs A5...A8
24 V AC power supply
System connector, 6-pole
IP 20, EN 60 529
Operation
Storage
Transport
Ambient/Storage/Transport
Modular installation device
Plastic housing, grey
On 35 mm mounting rail
90 x 72 x 69.5 mm (H x W x D)
70 mm / 4 modules at 18 mm
approx. 150 g
as required
EIB / KNX
in accordance with the EMC guideline and low
voltage guideline
Note:
Programming of the Analogue Actuator Module AAM/S 4.1
is implemented via the application of the Analogue Actuator
AA/S 4.1. The programming requires EIB Software Tool ETS2
V1.3 or higher. If ETS3 is used a ".VD3" type file must be im-
ported. The application program is available in the ETS2 / ETS3
at ABB/output/analogue output.
24 V AC ± 10 %
Max. 120 mA
Max. 6 mA
Outputs A5...A8
0 ... 1 V DC
0 ... 20 mA
0 ... 10 V DC 4 ... 20 mA
depending on parameterisation
Voltage signal:
1 kΩ
500 Ω
Current signal:
Max. 10 mA per channel
Max. 20 mA per channel
Status LED (red)
Status LED (yellow)
2 screw terminals per output/terminal
Conductor cross-section:
single-core: 0.50 – 4.0 mm²
stranded:
0.34 – 4.0 mm²
stranded:
0.14 – 2.5 mm²
Connection to analogue actuator
– 5 °C ... + 45 °C
– 25 °C ... + 70 °C
– 25 °C ... + 70 °C
Max. 93 % relative humidity, no condensation
to DIN EN 50 022