ABB i-bus EIB/KNX AA/S 4.1 Product Manual page 18

Analogue actuator,analogue actuator module. intelligent installation systems
Table of Contents

Advertisement

ABB i-bus
EIB / KNX
®
16
Commissioning
8-15
Analogue output
1-bit objects with which the output is forced to switch to a parameterised value. The output
assumes the previous value when forced control is switched off.
If both forced control 1 and forced control 2 are active, forced control 1 has priority.
The forced control objects can be time monitored. (see also object "Alarm Output ...")
The object "Forced control ..." of an output is only visible if the parameter "Forced control object
..." is set to "Forced control active with ...".
16-19 Analogue output
1-bit objects, which are used to switch the output on (100 %) or off.
This object can only be associated for example with the 1-bit object of a dim switch. It is only
available in 8-bit mode.
The switch object is not monitored if cyclic monitoring of the input value is active.
The objects "Switching" of an output is only visible if the parameter "Input format" is set to
"8 Bit".
20-23 Analogue output
4-bit object, to increase or decrease the output value continuously with a dim switch. The dim
speed is adjustable.
According to the EIB / KNX standard "dimming on" is possible and "dimming off" is not
possible.
The dim object is not monitored if cyclic monitoring of the input value is active.
The objects "Dimming" of an output is only visible if the parameter "Input format" is set to
"8 Bit".
24-27 Analogue output
1-bit object which is set if the output is overloaded in mode 0 ... 1 V or 0 ... 10 V
(output current above 10 mA), or if the monitoring time with active cyclic monitoring of the
communication objects "Input value" and / or "Force control ..." has timed out.
Forced control 1/2
1 Bit EIS 1
Output 1...4
DPT 1.001
Switching
1 Bit EIS 1
Output 1...4
DPT 1.001
Dimming
4 Bit EIS 2
Output 1...4
DPT 3.007
Alarm
1 Bit EIS 1
Output 1...4
DPT 1.005
C, W
C, W
C, W
C, T

Advertisement

Table of Contents
loading

This manual is also suitable for:

I-bus eib/knx aam/s 4.1

Table of Contents