ABB i-bus
EIB / KNX
®
5.4

Forced control

24
Planning and application
Both in the 8-bit as well as the 16-bit mode every output features up to two
1-bit communication objects, which enable control with a higher priority.
In order to use these objects the corresponding parameter must be set in
the parameter "Forced control object ...". By default these parameters are
set to "not available". Accordingly, the ETS does not show these
communication objects.
Forced control can be active if the object features either the value "1" or
the value "0". For the active state a fixed value is set with the parameter
"Output value in case of forced control". If the "Forced control" object
is inactive, the output automatically assumes the value which corresponds
with the "Input value" object.
If both "Forced control" objects are active, the object "Forced
control 1" has an internal priority over the object "Forced control 2".