ABB i-bus
EIB / KNX
®
18
Commissioning
37-44 Extension module
1-bit objects with which the output is forced to switch to a parameterised value. The output
assumes the previous value when forced control is switched off.
If both forced control 1 and forced control 2 are active, forced control 1 has priority.
The forced control objects can be time monitored. (see also object "Alarm Output ...")
The object "Forced control ..." of an output is only visible if the parameter "Forced
control object ..." is set to "Forced control active with ...".
45-48 Extension module
1-bit objects, which are used to switch the output on (100 %) or off.
This object can only be associated for example with the 1-bit object of a dim switch. It is only
available in 8-bit mode.
The switch object is not monitored if cyclic monitoring of the input value is active.
The objects "Switching" of an output is only visible if the parameter "Input format" is set to
"8 Bit".
49-52 Extension module
4-bit object, to increase or decrease the output value continuously with a dim switch. The dim
speed is adjustable.
According to the EIB / KNX standard "dimming on" is possible and "dimming off" is not
possible.
The dim object is not monitored if cyclic monitoring of the input value is active.
The objects "Dimming" of an output is only visible if the parameter "Input format" is set to
"8 Bit".
53-56 Extension module
1-bit object which is set if the output is overloaded in mode 0 ... 1 V or 0 ... 10 V
(output current above 10 mA), or if the monitoring time with active cyclic monitoring of the
communication objects "Input value" and / or "Force control ..." has timed out.
57
Extension module
1-bit object which is set if the supply voltage (24 V AC) of the analogue actuator module fails.
Telegram value: "0": power supply ok
Forced control 1/2
1 Bit EIS 1
Output 5...8
DPT 1.001
Switching
1 Bit EIS 1
Output 5...8
DPT 1.001
Dimming
4 Bit EIS 2
Output 5...8
DPT 3.007
Alarm
1 Bit EIS 1
Output 5...8
DPT 1.005
Alarm
1 Bit EIS 1
DPT 1.001
"1": failure of the power supply
C, W
C, W
C, W
C, T
C, T